Delta Electronics VFD-G manual Emergency Stop by DC Brake

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 71
Image 71
Emergency Stop by DC Brake

Chapter 4 ParametersManual backgroundManual backgroundManual backgroundManual backgroundManual background

Emergency Stop by DC Brake

Applications

Purpose

Functions

Related

Parameters

 

 

 

 

 

 

 

 

 

AC motor drive can use DC brake for

08-00

High-speed rotors

Emergency stop

emergency stop when a quick stop is

08-02

without brake

needed without brake resistor. When

08-03

 

resistor

used often, take motor cooling into

 

 

 

 

consideration.

 

 

 

 

 

Over-torque Setting

 

 

 

Applications

Purpose

Functions

Related

Parameters

 

 

 

 

 

The over-torque detection level can be

06-03~06-05

 

To protect

set. Once OC stall, OV stall and over-

 

 

torque occurs, the output frequency

 

Pumps, fans and

machines and to

 

will be adjusted automatically. It is

 

extruders

have continuous/

 

suitable for machines like fans and

 

 

reliable operation

 

 

pumps that require continuous

 

 

 

 

 

 

operation.

 

 

 

 

 

Upper/Lower Limit Frequency

 

 

Applications

Purpose

Functions

Related

Parameters

 

 

 

 

Control the motor

When user cannot provide

01-07

Pump and fan

upper/lower limit, gain or bias from

01-08

speed within

 

upper/lower limit

external signal, it can be set

 

 

individually in AC motor drive.

 

 

 

 

Skip Frequency Setting

 

 

Applications

Purpose

Functions

Related

Parameters

 

 

 

 

 

The AC motor drive cannot run at

08-11~08-16

Pumps and fans

To prevent

constant speed in the skip frequency

 

range. Three skip frequency ranges

 

machine vibrations

 

 

can be set. It is used to smooth

 

 

 

 

 

 

vibration at certain frequencies.

 

 

 

 

 

Carrier Frequency Setting

 

 

Applications

Purpose

Functions

Related

Parameters

 

 

 

 

 

The carrier frequency can be

02-03

General application

Low noise

increased when required to reduce

 

 

 

motor noise.

 

4-20

Revision July 2008, EG03, SW V1.06