Chapter 4 Parameters
The allowable power loss time must in the condition that AC drive auxiliary power is working normally. If auxiliary power is turned off in the allowable power loss time, the actual allowable power loss time will be shorter than the parameter setting.
08 - 06 | Speed Search Time | Unit: 0.1 | |
| Settings | 0.1~5.0 Sec | Factory Setting: 0.5 |
|
|
|
|
This parameter determines the delay time from fault (power loss, OV, OC or BB) recovery to start to execute the function of speed search time.
08 - 07 | Maximum Speed Search Current | Unit: 1 | |
| Settings | 30~150% | Factory Setting: 110 |
|
|
|
|
This parameter determines maximum current of speed search.
Maximum speed search current will have influence with synchronization attained time. The greater this parameter is set, the faster it will be synchronization. But if the parameter setting value is too great, it may occur
If
If
| Maximum allowable |
|
|
|
|
|
|
|
| Max. Allowable | ||||||||||
| power loss time |
|
|
|
|
|
|
|
| Power Loss Time | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Input |
|
|
|
|
|
|
|
|
|
|
| Speed | ||||||||
|
|
|
|
|
| Speed Search |
| Synchronization | ||||||||||||
|
|
|
|
|
|
| Detection | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
| |||||||||||||
Output |
|
|
|
| B.B. Time |
|
|
|
|
|
|
|
|
|
|
|
| B.B.Time |
|
|
Frequency |
|
|
|
|
|
|
| |||||||||||||
Output |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Momentary Power Loss Operation
Revision July 2008, EG03, SW V1.06 |