Chapter 4 Parameters

 

 

Parameter

Functions

Settings

Factory

Customer

 

 

 

Setting

 

 

 

 

 

 

 

 

06-06

Electronic Thermal

00: Operate disabled.

02

 

 

 

 

 

Relay Selection

01: Operate with a standard motor.

 

 

 

 

 

 

 

02: Operate with a special motor.

 

 

 

06-07

Electronic Thermal

30~600 Sec

60

 

 

 

 

 

Characteristic

 

 

 

 

06-08

Low Current Detection

00~100% (00 disabled)

00

 

 

 

 

 

Level

 

 

 

 

06-09

Low Current Detection

0.1~ 3600.0 Sec

10.0

 

 

 

 

 

Time

 

 

 

 

06-10

Low Current Detection

00: Warn and Ramp to stop

01

 

 

 

 

 

Treatment

01: Warn and Coast to stop

 

 

 

 

 

 

 

02: Warn and keep operating

 

 

 

06-11

Present Fault Record

00: No Fault

00

 

 

 

 

 

 

01: Oc (over-current)

 

 

 

06-12

Second Most Recent

00

 

 

02: Ov (over-voltage)

 

 

 

 

 

Fault Record

 

 

 

 

 

 

03: OH (over temperature)

 

 

 

06-13

Third Most Recent

00

 

 

04: OL (over load)

 

 

 

 

 

Fault Record

 

 

 

 

 

 

05: oL1 (over load 1)

 

 

 

06-14

Fourth Recent Fault

00

 

 

06: EF (external fault)

 

 

 

 

 

Record

07: Occ (IGBT module is abnormal)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08: CF3 (driver’s internal circuitry is

 

 

 

 

 

 

 

abnormal)

 

 

 

 

 

 

 

09: HPF (hardware protection failure)

 

 

 

 

 

 

 

10: OcA (over-current during acceleration)

 

 

 

 

 

 

 

11: Ocd (over-current during deceleration)

 

 

 

 

 

 

 

12: Ocn (over-current during steady state

 

 

 

 

 

 

 

operation)

 

 

 

 

 

 

 

13: GFF(Ground Fault)

 

 

 

 

 

 

 

14: Lv (Low voltage)

 

 

 

 

 

 

 

15: CF1 (CPU READ failure)

 

 

 

 

 

 

 

16: CF2 (CPU WRITE failure)

 

 

 

 

 

 

 

17: bb (Base Block)

 

 

 

 

 

 

 

18: OL2 (over load2)

 

 

 

 

 

 

 

19: Reserved

 

 

 

 

 

 

 

20: Code (software/password protection)

 

 

 

 

 

 

 

21: EF1 (Emergency stop)

 

 

 

 

 

 

 

22: PHL (phase-loss)

 

 

 

 

 

 

 

23: Lc (Low Current)

 

 

 

 

 

 

 

24: FbL(Feedback Loss)

 

 

 

 

 

 

 

25: Reserved

 

 

 

 

 

 

 

26: FANP (Fan Power Fault)

 

 

 

 

 

 

 

27: FF1 (Fan 1 Fault)

 

 

 

 

 

 

 

28: FF2 (Fan 2 Fault)

 

 

 

 

 

 

 

29: FF3 (Fan 3 Fault)

 

 

 

 

 

 

 

30: FF123 (Fan 1, 2, 3 Fault)

 

 

 

4-12

Revision July 2008, EG03, SW V1.06

Page 63
Image 63
Delta Electronics VFD-G manual Parameter Functions Settings Factory