Delta Electronics VFD-G manual 09 - 05 Even/Odd Parity and Stopping Parity Setting Factory Setting

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 121
Image 121
09 - 05 Even/Odd Parity and Stopping Parity Setting

Chapter 4 ParametersManual background

09 - 05 Even/Odd Parity and Stopping Parity Setting

Factory Setting: 00

Settings

00: None parity + 2 stop bit

 

01: Even parity + 2 stop bit

 

02: Odd parity + 2 stop bit

 

03: None parity + 1 stop bit

 

04: Even parity + 1 stop bit

 

05: Odd parity + 1 stop bit

 

 

This parameter determines the communication format of serial communication.

09 - 06 Communication Operation Command 1

Factory Setting: 00

Settings

Bit0~1: 00: Disabled

 

01: Stop

 

10: Start-up

 

11: JOG start-up

 

Bit2~3: Reserved

 

Bit4~5: 00: Disabled

 

01: FWD command

 

10: REV command

 

11: Direction change command

 

Bit6~7: 00: 1st step acce/decel speed

 

01: 2nd step acce/decel speed

 

10: 3rd step acce/decel speed

 

11: 4th step acce/decel speed

 

Bit8~11: 0000: Master speed

 

0001: 1st step speed

 

0010: 2nd step speed

 

0011: 3rd step speed

 

0100: 4th step speed

 

0101: 5th step speed

 

0110: 6th step speed

 

0111: 7th step speed

 

1000: 8th step speed

 

1001: 9th step speed

 

1010: 10th step speed

 

1011: 11th step speed

 

1100: 12th step speed

 

1101: 13th step speed

 

1110: 14th step speed

 

1111: 15th step speed

 

Bit12: Select Bit6~11 function

 

Bit13~15: Reserved

4-70

Revision July 2008, EG03, SW V1.06

Page 121
Image 121
Delta Electronics VFD-G manual 09 - 05 Even/Odd Parity and Stopping Parity Setting Factory Setting