Delta Electronics VFD-G manual Motor cannot Run, Troubleshooting, Revision July 2008, EG03, SW

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 147
Image 147
5.9 Motor cannot Run

Chapter 5 Troubleshooting Manual background

5.9 Motor cannot Run

 

 

 

 

 

Check PU01

No

 

Motor cannot run

 

 

 

for normal

 

 

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

Yes

 

Reset after clearing

Yes Check if there is any

fault and then RUN

 

 

 

fault code displayed

No

Check if non-fuse breaker and magnetic contactor are ON

 

Yes

 

Check if input

No

voltage is normal

 

 

Yes

 

 

 

 

 

 

NoManual background Set them to ON

Check if any faults occur, such as Lv, PHL or disconnection

It can run when

Input "RUN"

No

If jumper or DC reactor No

no faults occur

 

command

 

 

is connected between

 

 

 

 

 

 

by keypad

 

 

+1 and +2(+2/B1)

Use jumper or DC reactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Press RUN key to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

check if it can run

 

 

 

 

 

 

 

 

 

 

Maybe AC motor drive has malfunction or misoperation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

due to noise. Please contact DELTA.

 

 

 

 

 

Press UP key to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Check if input FWD

 

No

Check if the wiring

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or REV command

 

 

 

 

 

 

of FWD-DCM and

 

 

Change switch or relay

 

 

Press UP to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REV-DCM is correct

 

 

 

 

 

 

 

 

 

check if motor

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

can run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

No

No Set frequency or not

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct connection

 

 

 

 

 

 

 

 

 

 

 

Modify frequency

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

if upper bound freq.

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if the parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and setting freq. is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lower than the min.

 

 

 

 

 

 

 

setting and wiring of

 

Yes

 

Change defective

 

 

 

 

 

 

 

 

 

 

 

 

output freq.

 

 

 

 

 

 

 

analog signal and

 

 

 

 

potentiometer and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

multi-step speed

 

 

 

 

relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are correct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor has malfunction

 

 

 

Check if there is any

 

 

No

 

Maybe AC motor drive has malfunction.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output voltage from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

terminals U, V and W

 

Please contact DELTA.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If load is too large

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if motor

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if the setting

 

 

 

 

 

 

connection

 

 

 

 

Connect correctly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

is correct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is correct

 

 

 

 

 

 

 

Motor is locked due to large load, please reduce load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

For example, if there is a brake, check if it is released.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Increase the setting of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

torque compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-6

Revision July 2008, EG03, SW V1.06

Page 147
Image 147
Delta Electronics VFD-G manual Motor cannot Run, Troubleshooting, Revision July 2008, EG03, SW