Delta Electronics VFD-G manual Description of Parameter Settings

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 74
Image 74
4.3 Description of Parameter Settings

Chapter 4 Parameters: This parameter can be set during operation.

4.3 Description of Parameter Settings

Group 0: User Parameters

: This parameter can be set during operation.

00 - 00 Software Version

Factory setting: Read Only

This parameter displays the software version of AC drive.

00 - 01 AC Drive Status Indication 1

 

 

 

 

Factory setting: Read Only

 

This parameter displays the AC drive status.

 

 

 

 

 

Code

AC Drive Status

Explanation

 

00

No fault occurred

 

 

 

01

oc

over current

 

02

ov

over voltage

 

03

oH

over temperature

 

04

oL

overload

 

05

oL1

electronic thermal relay

 

06

EF (external fault)

EF-DCM is closed

 

07

occ (AC drive IGBT fault )

IGBT short circuit protection

 

08

CF3 (CPU failure)

Abnormal A/D reading during self-check

09

HPF (hardware protection

Hardware protection function activated during self-check.

 

 

failure)

 

 

10

ocA (over current during

Output current exceeds protection level during

 

 

acceleration)

acceleration

11

ocd (over current during

Output current exceeds protection level during

 

 

deceleration)

deceleration

12

Ocn (over current during

Output current exceeds protection level during steady

 

 

steady state)

state operation.

 

13

GFF (ground fault)

Ground fault protection feature activated

 

14

Lv (under voltage)

Low input voltage

 

15

CF1

EEPROM input data is abnormal

 

16

CF2

EEPROM output data is abnormal

 

17

bb (base block)

BB is set and activated

 

18

oL2 (over load 2)

Output current exceeds rated motor current

 

19

Reserved

 

 

 

20

codE

software or password protection

21

EF1 (external emergency

EF1 (a multifunction-DCM is enabled)

 

 

stop)

 

 

Revision July 2008, EG03, SW V1.06

4-23

Page 74
Image 74