Chapter 4 Parameters
4.3 Description of Parameter Settings
Group 0: User Parameters | : This parameter can be set during operation. |
00 - 00 Software Version
Factory setting: Read Only
This parameter displays the software version of AC drive.
00 - 01 AC Drive Status Indication 1
|
|
|
| Factory setting: Read Only |
| This parameter displays the AC drive status. | |||
|
|
|
| |
| Code | AC Drive Status | Explanation | |
| 00 | No fault occurred |
|
|
| 01 | oc | over current | |
| 02 | ov | over voltage | |
| 03 | oH | over temperature | |
| 04 | oL | overload | |
| 05 | oL1 | electronic thermal relay | |
| 06 | EF (external fault) | ||
| 07 | occ (AC drive IGBT fault ) | IGBT short circuit protection | |
| 08 | CF3 (CPU failure) | Abnormal A/D reading during | |
09 | HPF (hardware protection | Hardware protection function activated during | ||
|
| failure) |
|
|
10 | ocA (over current during | Output current exceeds protection level during | ||
|
| acceleration) | acceleration | |
11 | ocd (over current during | Output current exceeds protection level during | ||
|
| deceleration) | deceleration | |
12 | Ocn (over current during | Output current exceeds protection level during steady | ||
|
| steady state) | state operation. | |
| 13 | GFF (ground fault) | Ground fault protection feature activated | |
| 14 | Lv (under voltage) | Low input voltage | |
| 15 | CF1 | EEPROM input data is abnormal | |
| 16 | CF2 | EEPROM output data is abnormal | |
| 17 | bb (base block) | BB is set and activated | |
| 18 | oL2 (over load 2) | Output current exceeds rated motor current | |
| 19 | Reserved |
|
|
| 20 | codE | software or password protection | |
21 | EF1 (external emergency | EF1 (a | ||
|
| stop) |
|
|
Revision July 2008, EG03, SW V1.06 |