Delta Electronics VFD-G Time, Over-current Stall Prevention during Acceleration, Unit, Settings

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 103
Image 103
Time

Chapter 4 ParametersOver-current Stall Prevention during Acceleration

Group 6: Protection Function Parameters

06 - 00 Over-voltage Stall Prevention

Factory Setting: 780.0

Settings 660.0V~820.0VDC 00: Disabled

This parameter selects the voltage level for the Over-Voltage Stall Prevention function. During decelerations, the DC bus voltage may exceed its maximum allowable value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating and maintain a constant output frequency. The AC drive will only resume deceleration when the voltage drops below the preset value.

With moderate inertial loads, the over-voltage stall prevention will not occur and the deceleration time should be equal to Pr.1-10. With high inertial loads, the AC drive will automatically extend the deceleration time due to the step function shown below. If the deceleration time is critical for the application, then dynamic braking resistors should be used.

 

 

 

Output frequency

Deceleration characteristic

 

 

 

 

 

 

 

when Over-voltage stall

 

 

 

 

 

 

 

prevention enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency held

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deceleration Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06 - 01

Over-current Stall Prevention during Acceleration

Unit: 1

 

 

Settings

20~250%

 

 

 

 

 

 

 

 

Factory Setting: 150%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This parameter selects the percentage of allowable over-current during acceleration before the stall prevention is enabled.

During acceleration, the AC drive output current may increase abruptly and exceed the value specified by Pr.06-01 due to rapid acceleration or excessive load on the motor. When this function is enabled, the AC drive will stop accelerating and maintain a constant output frequency. The AC drive will only resume acceleration when the current drops below the value set in Pr.06-01 (please see the graph below).

4-52

Revision July 2008, EG03, SW V1.06

Page 103
Image 103
Delta Electronics VFD-G manual Time, Over-current Stall Prevention during Acceleration, Unit, Settings, 20~250%