Hearth and Home Technologies TRUE-50, TRUE-42 Top Vent Horizontal Termination Three Elbows

Page 29

1. Top Vent - Horizontal Termination - (continued)

Three Elbows

Note: Flue restrictor is permit- ted ONLY on 30 ft. minimum vertical runs with no elbows.

WARNING! Risk of Fire!

TRUE-36(NG/LP), TRUE-42(NG/LP) and TRUE-50 (NG/LP) models require a minimum of 24 inches of vertical venting before attaching any elbow to the appliance.

DO NOT attach elbow directly to the appliance.

H2

V2

H1

V1

TRUE-36 (NG/LP), TRUE-42 (NG/LP), TRUE-50 (NG/LP)

 

V1

 

H1

V2

H2

2 ft

610 mm

7 in

178 mm

*

H2 Max = 2 X V2

3 ft

914 mm

2 ft

610 mm

*

H2 Max = 2 X V2

4 ft

1.2 m

4 ft

1.2 m

*

H2 Max = 2 X V2

5 ft

1.5 m

9 ft

2.7 m

*

H2 Max = 2 X V2

6 ft

1.8 m

12 ft

3.7 m

*

H2 Max = 2 X V2

7 ft

2.1 m

14 ft

4.3 m

*

H2 Max = 2 X V2

10 ft

3.0 m

20 ft

6.1 m

*

H2 Max = 2 X V2

V1 + H1 must be adhered to.

* V2 has no specific restrictions EXCEPT,

Ht max = 2 x Vt and Vtotal + Htotal cannot exceed 60 ft Maximum

Figure 7.5

Heat & Glo • TRUE-36, TRUE-42, TRUE-502282-900 Rev. D • 8/12

29

Image 29
Contents What to do if you smell gas ModelsDo Discardnot HOT SurfacesHomeowner Reference Information CongratulationsUser Guide Table of ContentsReference Materials Appliance SetupTroubleshooting Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Remote Controls, Wall Controls and Wall Switches Fixed Glass AssemblyIPI Battery Tray/Battery Installation Clear SpaceNine Hour Safety Shutdown Feature Module ResetControl Module Operation Before Lighting FireplaceFinal inspection by Lighting Instructions IPIWhat to do if YOU Smell GAS GAS ValveAfter Fireplace is Lit Frequently Asked QuestionsIssue Solutions Maintenance and Service Glass Cleaning Exterior and Interior of Installed Glass Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection D ReplacementIPI Pilot Flame Patterns Burner Ignition and OperationTypical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Any such action may cause a fire hazardSelecting Appliance Location Framing and ClearancesTRUE-36 TRUE-42Clearances Minimum Framing DimensionsConstructing the Appliance Chase Non-Combustible Zone Mantel and Wall ProjectionsCombustible Mantel Legs or Wall Projections Non-Combustible Mantel Legs or Wall ProjectionsCombustible Mantel Projections 21 MINNON-COMBUSTIBLE Material TRUE-50Model Hearth ExtensionVent Termination Minimum Clearances Termination LocationsCovered Alcove Applications Ft. Canada ..........not to be installed above a gas meter Vent Information and Diagrams TRUE-36 NG/LP, TRUE-42 NG Top Vent Horizontal Termination One ElbowTRUE-50 NG/LP V1 Minimum Maximum+ H Two ElbowsTRUE-36 NG/LP, TRUE-42 NG/LP MinimumTRUE-36 NG/LP, TRUE-42 NG/LP, TRUE-50 NG/LP Top Vent Horizontal Termination Three ElbowsFlue Restrictor Elbows Top Vent Vertical TerminationTRUE-36 NG/LP, TRUE-42 NG/LP, TRUE-50 NG/LP Ht Max Top Vent Vertical Termination Three ElbowsPVI-SLP PVK-80 and PVI-SLP InformationPipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Non-Combustible Wall PenetrationPipe DVP Install the Ceiling FirestopInstalling the Optional Heat-ZoneGas Kit Install Attic Insulation ShieldFlat Ceiling Installation Vaulted Ceiling InstallationVent Preparation Appliance PreparationSide Nailing Tab in Shipping Position Securing and Leveling the ApplianceInstalling Non-Combustible Facing Material Installing Non-combustible Facing MaterialAttach Vent to the Firebox Assembly Installing Vent Pipe DVP PipeAssemble Vent Sections Assemble Pipe SectionsDisassemble Vent Sections Secure the Vent SectionsAssemble and Install Storm Collar Install Metal Roof FlashingHeat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Horizontal Termination Cap Fuel Conversion Gas InformationGas Pressure Gas ConnectionIntelliFire PlusTM Ignition System Wiring Wiring RequirementsOptional Accessories Requirements Electrical InformationAccess Through Left Column Access Through Firebox Electrical Service and Repair Junction Box InstallationFinishing Templates Template installation instructionFinishing Finishing Templates Bends Inoperable Fixed Doors Splatter GuardFACTORY-SUPPLIED NON-COMBUSTIBLE Combustible or Board 10 Combustible Mantel Allowance TRUE-36, TRUE-42 MAX 21 MINFacing Material 14 Non-combustible Facing DiagramDoors Dimension Inoperable Operable DoorArch Operable DoorsAppliance Setup LED’s Glowing Ember PlacementModels TRUE-36C, TRUE-36H, TRUE-36S Install the Log Assembly Log Set Assembly LOGS-TRUE36LOG Contacts Side Grate Tine Notch forLOG Contacts Left Grate Tine TineLOG Contacts Grate Tine LOG #7 TRUE-42 only Back Tine LOG Contacts Refractory Notch Front TineLOG #4 LOG Placement Slots NotchFlat Area Notch for For LOG #3TOP of Burned Area Near LOG #1 LOG Resting in Notch LOG Contacts 8 Grate Tine Back Tine Front Tine LOG Contacts Refractory NotchTRUE-36 TRUE-42 TRUE-50 TOP Retaining Rail Notch Glass Frame Notch Model TRUE-36 Air Shutter SettingTRUE-42 TRUE-50IntelliFire Plus Ignition System TroubleshootingSymptom Possible Cause Corrective Action Troubleshooting Location Inches Millimeters Appliance Dimension DiagramReference Materials Appliance Dimensions TRUE-42 & TRUE-50 DVP-AS2 Vent Components DiagramsHorizontal Termination Cap DVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2DVP-TRAP BEK DVP-BEK2 RF6M RF12MDVP-TRAPFL COOL-ADDPower Vent Inline Optional Wire HarnessDescription Part Number SLP-LPCCService. ServicePartsParts Log Set AssemblyAt Depot Description Comments Part NumberDescription Comments Part Number Service PartsStocked Log Set Assembly TRUE-42S, TRUE-42H, TRUE-42C LOGS-TRUE50 TRUE-50S, TRUE-50H, TRUE-50C TRUE-36, TRUE-42, TRUE-50 #13 Valve AssemblyMYSTIC-EMBERS Contact Information