Hearth and Home Technologies TRUE-50, TRUE-42 Requirements for the Commonwealth of Massachusetts

Page 8

Note: The following requirements reference various Massachusetts and national codes not contained in this document.

H.Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addi- tion, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detec- tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu- eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur- ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor- dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu- eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB- STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon- tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob- serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fu- eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro- vide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment in- stallation instructions; and

The “special venting systems” shall be Product Ap- proved by the Board, and the instructions for that sys- tem shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Ap- proved side wall horizontally vented gas fueled equip- ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

See Gas Connection section for additional Common- wealth of Massachusetts requirements.

8

Heat & Glo • TRUE-36, TRUE-42, TRUE-502282-900 Rev. D • 8/12

Image 8
Contents Models What to do if you smell gasDo Discardnot HOT SurfacesCongratulations Homeowner Reference InformationTable of Contents User GuideReference Materials Appliance SetupTroubleshooting Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Installation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsYour Fireplace Gas Fireplace SafetyOperating Instructions User Guide Fixed Glass Assembly Remote Controls, Wall Controls and Wall SwitchesIPI Battery Tray/Battery Installation Clear SpaceModule Reset Nine Hour Safety Shutdown FeatureControl Module Operation Before Lighting FireplaceLighting Instructions IPI Final inspection byWhat to do if YOU Smell GAS GAS ValveAfter Fireplace is Lit Frequently Asked QuestionsIssue Solutions Maintenance and Service Maintenance Tasks-Qualified Service Technician Glass Cleaning Exterior and Interior of Installed GlassGasket Seal and Glass Assembly Inspection D ReplacementBurner Ignition and Operation IPI Pilot Flame PatternsGetting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Any such action may cause a fire hazardFraming and Clearances Selecting Appliance LocationTRUE-36 TRUE-42Clearances Minimum Framing DimensionsConstructing the Appliance Chase Mantel and Wall Projections Non-Combustible ZoneCombustible Mantel Legs or Wall Projections Non-Combustible Mantel Legs or Wall Projections21 MIN Combustible Mantel ProjectionsNON-COMBUSTIBLE Material TRUE-50Hearth Extension ModelTermination Locations Vent Termination Minimum ClearancesFt. Canada ..........not to be installed above a gas meter Covered Alcove ApplicationsVent Information and Diagrams Top Vent Horizontal Termination One Elbow TRUE-36 NG/LP, TRUE-42 NGTRUE-50 NG/LP V1 Minimum MaximumTwo Elbows + HTRUE-36 NG/LP, TRUE-42 NG/LP MinimumTop Vent Horizontal Termination Three Elbows TRUE-36 NG/LP, TRUE-42 NG/LP, TRUE-50 NG/LPFlue Restrictor Top Vent Vertical Termination ElbowsTop Vent Vertical Termination Three Elbows TRUE-36 NG/LP, TRUE-42 NG/LP, TRUE-50 NG/LP Ht MaxPVK-80 and PVI-SLP Information PVI-SLPVent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Non-Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVPInstall Attic Insulation Shield Installing the Optional Heat-ZoneGas KitFlat Ceiling Installation Vaulted Ceiling InstallationAppliance Preparation Vent PreparationSecuring and Leveling the Appliance Side Nailing Tab in Shipping PositionInstalling Non-combustible Facing Material Installing Non-Combustible Facing MaterialInstalling Vent Pipe DVP Pipe Attach Vent to the Firebox AssemblyAssemble Vent Sections Assemble Pipe SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Metal Roof Flashing Assemble and Install Storm CollarHeat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Horizontal Termination Cap Gas Information Fuel ConversionGas Pressure Gas ConnectionWiring Requirements IntelliFire PlusTM Ignition System WiringOptional Accessories Requirements Electrical InformationElectrical Service and Repair Junction Box Installation Access Through Left Column Access Through FireboxFinishing Templates Template installation instructionFinishing Splatter Guard Finishing Templates Bends Inoperable Fixed DoorsFACTORY-SUPPLIED NON-COMBUSTIBLE Combustible or Board MAX 21 MIN 10 Combustible Mantel Allowance TRUE-36, TRUE-4214 Non-combustible Facing Diagram Facing MaterialDimension Inoperable Operable Door DoorsArch Operable DoorsAppliance Setup Glowing Ember Placement LED’sInstall the Log Assembly Log Set Assembly LOGS-TRUE36 Models TRUE-36C, TRUE-36H, TRUE-36SLOG Contacts Side Grate Tine Notch forTine LOG Contacts Left Grate TineBack Tine LOG Contacts Refractory Notch Front Tine LOG Contacts Grate Tine LOG #7 TRUE-42 onlyLOG Placement Slots Notch LOG #4Flat Area Notch for For LOG #3TOP of Burned Area Near LOG #1 LOG Resting in Notch Back Tine Front Tine LOG Contacts Refractory Notch LOG Contacts 8 Grate TineTRUE-36 TRUE-42 TRUE-50 TOP Retaining Rail Notch Glass Frame Notch Air Shutter Setting Model TRUE-36TRUE-42 TRUE-50IntelliFire Plus Ignition System TroubleshootingSymptom Possible Cause Corrective Action Troubleshooting Location Inches Millimeters Appliance Dimension DiagramReference Materials Appliance Dimensions TRUE-42 & TRUE-50 Vent Components Diagrams DVP-AS2Horizontal Termination Cap DVP-TRAP1 DVP-TRAP2 DVP-TRAPK1 DVP-TRAPK2DVP-TRAP RF6M RF12M BEK DVP-BEK2DVP-TRAPFL COOL-ADDOptional Wire Harness Power Vent InlineDescription Part Number SLP-LPCLog Set Assembly CService. ServicePartsPartsAt Depot Description Comments Part NumberDescription Comments Part Number Service PartsStocked Log Set Assembly TRUE-42S, TRUE-42H, TRUE-42C LOGS-TRUE50 TRUE-50S, TRUE-50H, TRUE-50C #13 Valve Assembly TRUE-36, TRUE-42, TRUE-50MYSTIC-EMBERS Contact Information