Goodmans ASX, GSZ Checking Voltage, Checking Wiring, Checking THERMOSTAT, WIRING, and Anticipator

Page 35

SERVICING

S-1 CHECKING VOLTAGE

1.Remove outer case, control panel cover, etc., from unit being tested.

With power ON:

WARNING

Line Voltage now present.

2.Using a voltmeter, measure the voltage across terminals L1 and L2 of the contactor for the condensing unit or at the field connections for the air handler or heaters.

3.No reading - indicates open wiring, open fuse(s) no power or etc., from unit to fused disconnect service. Repair as needed.

4.With ample voltage at line voltage connectors, energize the unit.

5.Measure the voltage with the unit starting and operating, and determine the unit Locked Rotor Voltage. NOTE: If checking heaters, be sure all heating elements are energized.

Locked Rotor Voltage is the actual voltage available at the compressor during starting, locked rotor, or a stalled condition. Measured voltage should be above minimum listed in chart below.

To measure Locked Rotor Voltage attach a voltmeter to the run "R" and common "C" terminals of the compressor, or to the T1 and T2 terminals of the contactor. Start the unit and allow the compressor to run for several seconds, then shut down the unit. Immediately attempt to restart the unit while measuring the Locked Rotor Voltage.

6.Lock rotor voltage should read within the voltage tabula- tion as shown. If the voltage falls below the minimum voltage, check the line wire size. Long runs of undersized wire can cause low voltage. If wire size is adequate, notify the local power company in regard to either low or high voltage.

UNIT SUPPLY VOLTAGE

VOLTAGE

MIN.

MAX.

460

437

506

 

 

 

208/230

198

253

NOTE: When operating electric heaters on voltages other than 240 volts, refer to the System Operation section on electric heaters to calculate temperature rise and air flow. Low voltage may cause insufficient heating.

S-2 CHECKING WIRING

HIGH VOLTAGE!

Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

1.Check wiring visually for signs of overheating, damaged insulation and loose connections.

2.Use an ohmmeter to check continuity of any suspected open wires.

3.If any wires must be replaced, replace with comparable gauge and insulation thickness.

S-3 CHECKING THERMOSTAT, WIRING, AND ANTICIPATOR

THERMOSTAT WIRE SIZING CHART

LENGTH OF RUN

MIN. COPPER WIRE

GAUGE (AWG)

 

25 feet

18

50 feet

16

75 feet

14

100 feet

14

125 feet

12

150 feet

12

S-3A THERMOSTAT AND WIRING

WARNING

Line Voltage now present.

With power ON, thermostat calling for cooling

1.Use a voltmeter to check for 24 volts at thermostat wires C and Y in the condensing unit control panel.

2.No voltage indicates trouble in the thermostat, wiring or external transformer source.

3.Check the continuity of the thermostat and wiring. Repair or replace as necessary.

Indoor Blower Motor

With power ON:

WARNING

Line Voltage now present.

1.Set fan selector switch at thermostat to "ON" position.

2.With voltmeter, check for 24 volts at wires C and G.

3.No voltage indicates the trouble is in the thermostat or wiring.

35

Image 35
Contents Service Instructions Fax us at 713 Fax us at 931 438 Recognize Safety SYMBOLS, Words and LabelsEmail us at customerservice@goodmanmfg.com Important InformationSafe Refrigerant Handling Split System Heat Pumps R410A Product IdentificationModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 ASX13 AccessoriesDSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Condensing Unit Product DesignFigure a Capacity Control Cooling Cycle System OperationHeating CoolingHeating Cycle Defrost CycleCooling Cycle System Operation Description AFE18-60A Control BoardCOOLING/HP Analysis Chart Troubleshooting Chart61B ServicingChecking Voltage Checking WiringChecking THERMOSTAT, WIRING, and Anticipator 3A Thermostat and Wiring3C Heating Anticipator 3B Cooling AnticipatorChecking Cycle Protector Checking Time Delay RelayTesting Coil Circuit Checking Transformer Control CircuitChecking Contactor Contacts Testing Compressor ContactorSingle Phase Checking Contactor AND/OR RelaysTesting FAN Relay Copeland Comfort Alert DiagnosticsDiagnostics Table Checking Capacitor Checking Loss of Charge ProtectorChecking High Pressure Control Checking LOW Pressure ControlRELAY, Start 15A Resistance Check15B Capacitance Check 16B Checking FAN and Blower Motor ECM Motors 16A Checking FAN and Blower Motor Windings PSC MotorsChart on Next Chart from Previous 16C Checking ECM Motor Windings 16D ECM CFM Adjustments MBE / AepfCFM GE X13TM Motor Connections 16E Blower Performance Data16F Checking GE X13TM Motors 17B Ground Test Testing Compressor WindingsChecking Compressor 17A Resistance TestCompressor Ground Test 17C Unloader Test ProcedureUnloader Test Procedure 17D Operation TestChecking Reversing Valve and Solenoid Testing Crankcase Heater Optional ItemTesting Defrost Control Testing Defrost ThermostatSequence of Operation 40 MBR/AR*F Electronic Blower Time Delay RelayChecking Heater Limit Controls Checking Heater ElementsHeating Operation MBR/AR*F with Single Stage Heat PumpsMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41 MBE/AEPF with GSX, SSX, ASX, DSXDefrost Operation 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps MBE/AEPF with TWO Stage ASX & DSX Condensers Sequence of OperationMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item Formulas 61A Checking Heater Limit Controls61B Checking Heater Fuse Link Optional Electric Heaters Brazing Materials Leak Testing Nitrogen or NITROGEN-TRACEDRefrigeration Repair Practice EvacuationEvacuation ChargingChecking Compressor Efficiency Final Charge AdjustmentTXV Valves 105B Thermostatic Expansion ValvePressure vs. Temperature Chart 410A Required Liquid Line Temperature Checking Subcooling OverfeedingUnderfeeding SuperheatSubcooling Formula = Sat. Liquid Temp. Liquid Line 109A TWO Speed ApplicationChecking Expansion Valve Operation Fixed Orifice Restrictor DevicesCompressor Burnout Checking Restricted Liquid LineOvercharge of Refrigerant NON-CONDENSABLESTube Sizing Accessories for lines greater than 80 feetRefrigerant Piping Long Line SET Application R-410AInstallation Requirements Initial System Charging AIR Handler External StaticStatic Pressure Drop Coil Static Pressure DropTotal External Static ALL Fuel System AFE18-60A Control Board Accessories Wiring Diagrams10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF