Goodmans SSZ, GSZ, ASZ, SSX, ASX, DSZ, DSX, GSX Copeland Comfort Alert Diagnostics, Testing FAN Relay

Page 39

SERVICING

WARNING

Line Voltage now present.

4

3

OHMMETER

5

1

2

TESTING FAN RELAY

4.Using an ohmmeter, test between 2 and 4 - should read continuous . Test between 5 and 6 - should read open.

5.If not as above, replace the relay.

S-10 COPELAND COMFORT ALERT™

DIAGNOSTICS

Applies to ASX /ASZ and DSX/DSZ units

Comfort Alert™ is self-contained with no required external sensors and is designed to install directly into the electrical box of any residential condensing unit that has a Copeland Scroll™ compressor inside.

Once attached, Comfort Alert™ provides around-the-clock monitoring for common electrical problems, compressor defects and broad system faults. If a glitch is detected, an LED indicator flashes the proper alert codes to help you quickly pinpoint the problem. See Diagnostic Table on following page.)

39

Image 39
Contents Service Instructions Fax us at 713 Fax us at 931 438 Recognize Safety SYMBOLS, Words and LabelsEmail us at customerservice@goodmanmfg.com Important InformationSafe Refrigerant Handling Split System Heat Pumps R410A Product IdentificationModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 ASX13 AccessoriesDSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Condensing Unit Product DesignFigure a Capacity Control Cooling Cycle System OperationHeating CoolingHeating Cycle Defrost CycleCooling Cycle System Operation Description AFE18-60A Control BoardCOOLING/HP Analysis Chart Troubleshooting Chart61B ServicingChecking Voltage Checking WiringChecking THERMOSTAT, WIRING, and Anticipator 3A Thermostat and Wiring3C Heating Anticipator 3B Cooling AnticipatorChecking Cycle Protector Checking Time Delay RelayTesting Coil Circuit Checking Transformer Control CircuitChecking Contactor Contacts Testing Compressor ContactorSingle Phase Checking Contactor AND/OR RelaysTesting FAN Relay Copeland Comfort Alert DiagnosticsDiagnostics Table Checking Capacitor Checking Loss of Charge ProtectorChecking High Pressure Control Checking LOW Pressure Control15A Resistance Check 15B Capacitance CheckRELAY, Start 16B Checking FAN and Blower Motor ECM Motors 16A Checking FAN and Blower Motor Windings PSC MotorsChart on Next Chart from Previous 16C Checking ECM Motor Windings 16D ECM CFM Adjustments MBE / AepfCFM 16E Blower Performance Data 16F Checking GE X13TM MotorsGE X13TM Motor Connections 17B Ground Test Testing Compressor WindingsChecking Compressor 17A Resistance TestCompressor Ground Test 17C Unloader Test ProcedureUnloader Test Procedure 17D Operation TestChecking Reversing Valve and Solenoid Testing Crankcase Heater Optional ItemTesting Defrost Control Testing Defrost ThermostatSequence of Operation 40 MBR/AR*F Electronic Blower Time Delay RelayChecking Heater Limit Controls Checking Heater ElementsHeating Operation MBR/AR*F with Single Stage Heat Pumps41 MBE/AEPF with GSX, SSX, ASX, DSX Defrost OperationMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps MBE/AEPF with TWO Stage ASX & DSX Condensers Sequence of OperationMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item 61A Checking Heater Limit Controls 61B Checking Heater Fuse Link Optional Electric HeatersFormulas Brazing Materials Leak Testing Nitrogen or NITROGEN-TRACEDRefrigeration Repair Practice EvacuationEvacuation ChargingChecking Compressor Efficiency Final Charge AdjustmentTXV Valves 105B Thermostatic Expansion ValvePressure vs. Temperature Chart 410A Required Liquid Line Temperature Checking Subcooling OverfeedingUnderfeeding SuperheatSubcooling Formula = Sat. Liquid Temp. Liquid Line 109A TWO Speed ApplicationChecking Expansion Valve Operation Fixed Orifice Restrictor DevicesCompressor Burnout Checking Restricted Liquid LineOvercharge of Refrigerant NON-CONDENSABLESTube Sizing Accessories for lines greater than 80 feetRefrigerant Piping Long Line SET Application R-410AInstallation Requirements Initial System Charging AIR Handler External StaticCoil Static Pressure Drop Total External StaticStatic Pressure Drop ALL Fuel System AFE18-60A Control Board Accessories Wiring Diagrams10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF