Goodmans GSX, GSZ, ASZ, SSX, ASX, DSZ, DSX, SSZ manual Installation Requirements

Page 70

SERVICING

4.Two-Stage Condensing Unit: The maximum length of tubing must not exceed 80 feet where indoor coil is located above the outdoor unit.

NOTE: When the outdoor unit is located above the indoor coil, the maximum vertical rise must not exceed 25 feet. If the maximum vertical rise exceeds 25 feet, premature compressor failure will occur due to inad- equate oil return.

5.Most refrigerant tubing kits are supplied with 3/8"- thick insulation on the vapor line. For long line installations over 80 feet that pass through a high ambient temperature, ½”-thick suction line insula- tion is recommended to reduce loss of capacity. Insulate the liquid line if it passes through an area of 120°F or greater. Do not attach the liquid line to any non-insulated portion of the suction line.

6.Vibration and Noise: In long line applications, refriger- ant tubing is highly prone to transmit noise and vibration to the structure it is fastened to. Use adequate vibration- isolating hardware when mounting line set to adjacent structure.

Table 4 lists multiplier values to recalculate system-cooling capacity as a function of a system’s equivalent line length (as calculated from the suction line) and the selected suction tube size. Table 5 lists the equivalent length gained from adding bends to the suction line. Properly size the suction line to minimize capacity loss.

TABLE 4. CAPACITY MULTIPLIERS AS A FUNCTION OF SUCTION LINE SIZE & EQUIVALENT LENGTH

Nominal

Vapor line

 

EQUIVALENT LINE LENGTH (FT)

 

capacity

diameter

 

 

 

 

 

 

 

 

 

 

 

 

Btuh

(in.)

50

75

100

125

 

150

18,000

3/4

.99

.97

.96

.95

 

.95

24,000

3/4

1

.99

.99

.98

 

.97

30,000

3/4

.98

.97

.96

.95

 

.94

36,000

3/4

.93

.90

.86

.83

 

.79

7/8

.98

.96

.94

.92

 

.90

 

 

42,000

3/4

.93

.90

.87

.83

 

.80

7/8

.97

.96

.94

.93

 

.92

 

1-1/8

1

1

.99

.99

 

.98

48,000

3/4

.90

.86

.82

.78

 

N/R

7/8

.96

.94

.93

.91

 

.89

 

1-1/8

1

1

.99

.99

 

.98

60,000

7/8

.93

.91

.89

.86

 

.84

1-1/8

.99

.98

.98

.97

 

.97

 

 

NOTE: For a condenser with a liquid valve tube connection less than 3/8" diameter, use 3/8" liquid line tubing for a line set greater than 25 feet.

TABLE 5. LOSSES FROM SUCTION LINE ELBOWS

(EQUIVALENT LENGTH, FT.)

Type of elbow fitting

 

I.D. (in.)

 

3/4

7/8

1-1/8

 

90° short radius

1.7

2

2.3

90° long radius

1.5

1.7

1.6

45°

0.7

0.8

1

Installation Requirements

1.In a completely horizontal installation with a long line set where the evaporator is at the same altitude as (or slightly below) the condenser, the line set should be sloped towards the evaporator. This helps reduce refrigerant migration to the condenser during a system’s off-cycle.

2.For a system installation where the evaporator is above the condenser, an inverted vapor line trap should be installed on the suction line just before the inlet to the evaporator (see Fig 6). The top of the inverted loop must be slightly above the top of the evaporator coil and can be created simply by brazing two 90° long radius elbows together, if a bending tool is unavailable. Properly support and secure the inverted loop to the nearest point on the indoor unit or adjacent structure.

Fig 6. Evaporator unit with inverted vapor loop

3.An oil trap is required at the evaporator if the condenser is above the evaporator. Depending on the vertical rise of the line set, oil traps are required in the suction line. Oil traps should be installed at equal intervals along the suction line. Install 1 oil trap for a height difference of 15–25 feet between indoor and outdoor units. Install 2 oil traps for a difference of 26-50 ft, 3 for 51-100 ft, and 4 for 101-150 ft. Preformed oil traps are available at most HVAC supply houses, or oil traps may be created by brazing tubing elbows together (see diagram below). Remember to add the equivalent length from oil traps to the equivalent length calculation of the suction line. For example, if you construct an oil trap using two 45° elbows, one short and one long 90° elbow in a ¾” diameter suction line, the additional equivalent length would be 0.7+ 0.7+1.7+1.5, which equals 4.6 feet (refer to Table 5).

70

Image 70
Contents Service Instructions Important Information Recognize Safety SYMBOLS, Words and LabelsEmail us at customerservice@goodmanmfg.com Fax us at 713 Fax us at 931 438Safe Refrigerant Handling Product Identification Split System Heat Pumps R410AModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 Accessories ASX13DSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Product Design Condensing UnitFigure a Capacity Control Cooling System OperationHeating Cooling CycleDefrost Cycle Heating CycleCooling Cycle System Operation AFE18-60A Control Board DescriptionTroubleshooting Chart COOLING/HP Analysis ChartServicing 61B3A Thermostat and Wiring Checking WiringChecking THERMOSTAT, WIRING, and Anticipator Checking Voltage3B Cooling Anticipator 3C Heating AnticipatorChecking Transformer Control Circuit Checking Time Delay RelayTesting Coil Circuit Checking Cycle ProtectorChecking Contactor AND/OR Relays Testing Compressor ContactorSingle Phase Checking Contactor ContactsCopeland Comfort Alert Diagnostics Testing FAN RelayDiagnostics Table Checking LOW Pressure Control Checking Loss of Charge ProtectorChecking High Pressure Control Checking Capacitor15B Capacitance Check 15A Resistance CheckRELAY, Start 16A Checking FAN and Blower Motor Windings PSC Motors 16B Checking FAN and Blower Motor ECM MotorsChart on Next Chart from Previous 16D ECM CFM Adjustments MBE / Aepf 16C Checking ECM Motor WindingsCFM 16F Checking GE X13TM Motors 16E Blower Performance DataGE X13TM Motor Connections 17A Resistance Test Testing Compressor WindingsChecking Compressor 17B Ground Test17D Operation Test 17C Unloader Test ProcedureUnloader Test Procedure Compressor Ground TestTesting Defrost Thermostat Testing Crankcase Heater Optional ItemTesting Defrost Control Checking Reversing Valve and SolenoidChecking Heater Elements 40 MBR/AR*F Electronic Blower Time Delay RelayChecking Heater Limit Controls Sequence of OperationMBR/AR*F with Single Stage Heat Pumps Heating OperationDefrost Operation 41 MBE/AEPF with GSX, SSX, ASX, DSXMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps Sequence of Operation MBE/AEPF with TWO Stage ASX & DSX CondensersMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item 61B Checking Heater Fuse Link Optional Electric Heaters 61A Checking Heater Limit ControlsFormulas Evacuation Leak Testing Nitrogen or NITROGEN-TRACEDRefrigeration Repair Practice Brazing MaterialsCharging EvacuationFinal Charge Adjustment Checking Compressor Efficiency105B Thermostatic Expansion Valve TXV ValvesPressure vs. Temperature Chart 410A Required Liquid Line Temperature Superheat OverfeedingUnderfeeding Checking SubcoolingFixed Orifice Restrictor Devices 109A TWO Speed ApplicationChecking Expansion Valve Operation Subcooling Formula = Sat. Liquid Temp. Liquid LineNON-CONDENSABLES Checking Restricted Liquid LineOvercharge of Refrigerant Compressor BurnoutLong Line SET Application R-410A Accessories for lines greater than 80 feetRefrigerant Piping Tube SizingInstallation Requirements AIR Handler External Static Initial System ChargingTotal External Static Coil Static Pressure DropStatic Pressure Drop Accessories Wiring Diagrams ALL Fuel System AFE18-60A Control Board10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF