Goodmans ASZ, GSZ, SSX, ASX, DSZ, DSX, GSX, SSZ manual Troubleshooting Chart, COOLING/HP Analysis Chart

Page 33

TROUBLESHOOTING CHART

COOLING/HP ANALYSIS CHART

Com plaint

POSSIBLE CAUSE

SYMPTOM

DOTS IN ANALYSIS

 

GUIDE INDICATE

 

"POSSIBLE CAUSE"

 

Pow er Failure

Blow n Fuse

Unbalanced Pow er, 3PH

Loose Connection

Shorted or Broken Wires

Open Fan Overload

Faulty Thermostat

Faulty Transformer

Shorted or Open Capacitor

Internal Compressor Overload Open

Shorted or Grounded Compressor

Compressor Stuck

Faulty Compressor Contactor

Faulty Fan Relay

Open Control Circuit

Low V oltage

Faulty Evap. Fan Motor

Shorted or Grounded Fan Motor

Improper Cooling A nticipator

Shortage of Refrigerant

Restricted Liquid Line

Open Element or Limit on Elec. Heater

Dirty A ir Filter

Dirty Indoor Coil

Not enough air across Indoor Coil

Too much air across Indoor Coil

Overcharge of Refrigerant

Dirty Outdoor Coil

Noncondensibles

Recirculation of Condensing Air

Infiltration of Outdoor Air

Improperly Located Thermostat

Air Flow Unbalanced

System Undersized

Broken Internal Parts

Broken Valves

Inefficient Compressor

Wrong Type Expansion V alve

Expansion Device Restricted

Oversized Expansion Valve

Undersized Expansion V alve

Expansion Valve Bulb Loose

Inoperative Expansion V alve

Loose Hold-dow n Bolts

Faulty Reversing Valve

Faulty Defrost Control

Faulty Defrost Thermostat

Flow rator Not Seating Properly

startnot

willSystem

 

 

No Cooling

 

 

 

 

 

 

 

 

Uns atisfactory

 

 

 

 

 

 

 

 

 

 

Cooling/He ating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor will not start - fan runs

 

Comp. and Cond. Fan will not start

 

Evaporator fan will not start

 

Condenser fan will not start

 

Compressor runs - goes off on overload

 

Compressor cycles on overload

System runs continuously - little cooling/htg

 

Too cool and then too warm

 

Not cool enough on warm days

 

Certain areas too cool, others too warm

 

Compressor is noisy

 

System runs - blows cold air in heating

 

Unit will not terminate defrost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling or Heating Cycle (He at Pum p)

 

 

 

 

 

System

Operating

Pre ss ure s

Test Method

Remedy

will not defrost

suction pressure

head pressure

suction pressure

head pressure

Unit

Low

Low

High

High

Test V oltage

Inspect Fuse Size & Type

Test V oltage

Inspect Connection - Tighten

Test Circuits With Ohmmeter

Test Continuity of Overload

Test Continuity of Thermostat & Wiring

 

 

 

Check Control Circuit w ith V oltmeter

 

 

 

Test Capacitor

 

 

 

Test Continuity of Overload

 

 

 

Test Motor Windings

 

 

 

Use Test Cord

 

 

 

Test Continuity of Coil & Contacts

 

 

 

Test Continuity of Coil A nd Contacts

 

 

 

Test Control Circuit w ith Voltmeter

 

 

Test V oltage

 

Repair or Replace

 

 

Test Motor Windings

 

Check Resistance of A nticipator

Test For Leaks, Add Refrigerant

Remove Restriction, Replace Restricted Part

 

 

Test Heater Element and Controls

 

Inspect Filter-Clean or Replace

 

Inspect Coil - Clean

 

Check Blow er Speed, Duct Static Press, Filter

 

Reduce Blow er Speed

Recover Part of Charge

Inspect Coil - Clean

Recover Charge, Evacuate, Recharge

Remove Obstruction to Air Flow

Check Window s, Doors, V ent Fans, Etc. Relocate Thermostat

Readjust Air Volume Dampers Refigure Cooling Load

 

 

 

Replace Compressor

 

 

 

Test Compressor Efficiency

 

 

 

Test Compressor Efficiency

 

 

 

 

Replace V alve

 

 

 

 

 

 

 

Remove Restriction or Replace Expansion Device

 

 

 

 

 

Replace V alve

 

 

 

Replace V alve

 

 

 

Tighten Bulb Bracket

 

 

 

 

 

 

Check Valve Operation

 

 

 

 

 

 

 

Tighten Bolts

 

 

♦ ♦

Replace V alve or Solenoid

♦ ♦ ♦ Test Control

♦ ♦ ♦

 

 

Test Defrost Thermostat

 

 

 

 

Check Flow rator & Seat or Replace Flow rator

 

 

 

He ating Cycle Only (He at Pum p)

See Service Procedure Ref.

S-1

S-1

S-1

S-2, S-3

S-2, S-3

S-17A

S-3

S-4

S-15

S-17A

S-17B

S-17D

S-7, S-8

S-7

S-4

S-1

S-16

S-16

S-3B

S-101,103

S-112

S-26,S-27

S-200

S-200

S-113

S-114

S-115

S-104

S-104

S-110

S-110

S-105

S-110

S-21, 122

S-24

S-25

S-111

33

Image 33
Contents Service Instructions Email us at customerservice@goodmanmfg.com Recognize Safety SYMBOLS, Words and LabelsImportant Information Fax us at 713 Fax us at 931 438Safe Refrigerant Handling Split System Heat Pumps R410A Product IdentificationModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 ASX13 AccessoriesDSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Condensing Unit Product DesignFigure a Capacity Control Heating System OperationCooling Cooling CycleHeating Cycle Defrost CycleCooling Cycle System Operation Description AFE18-60A Control BoardCOOLING/HP Analysis Chart Troubleshooting Chart61B ServicingChecking THERMOSTAT, WIRING, and Anticipator Checking Wiring3A Thermostat and Wiring Checking Voltage3C Heating Anticipator 3B Cooling AnticipatorTesting Coil Circuit Checking Time Delay RelayChecking Transformer Control Circuit Checking Cycle ProtectorSingle Phase Testing Compressor ContactorChecking Contactor AND/OR Relays Checking Contactor ContactsTesting FAN Relay Copeland Comfort Alert DiagnosticsDiagnostics Table Checking High Pressure Control Checking Loss of Charge ProtectorChecking LOW Pressure Control Checking Capacitor15A Resistance Check 15B Capacitance CheckRELAY, Start 16B Checking FAN and Blower Motor ECM Motors 16A Checking FAN and Blower Motor Windings PSC MotorsChart on Next Chart from Previous 16C Checking ECM Motor Windings 16D ECM CFM Adjustments MBE / AepfCFM 16E Blower Performance Data 16F Checking GE X13TM MotorsGE X13TM Motor Connections Checking Compressor Testing Compressor Windings17A Resistance Test 17B Ground TestUnloader Test Procedure 17C Unloader Test Procedure17D Operation Test Compressor Ground TestTesting Defrost Control Testing Crankcase Heater Optional ItemTesting Defrost Thermostat Checking Reversing Valve and SolenoidChecking Heater Limit Controls 40 MBR/AR*F Electronic Blower Time Delay RelayChecking Heater Elements Sequence of OperationHeating Operation MBR/AR*F with Single Stage Heat Pumps41 MBE/AEPF with GSX, SSX, ASX, DSX Defrost OperationMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps MBE/AEPF with TWO Stage ASX & DSX Condensers Sequence of OperationMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item 61A Checking Heater Limit Controls 61B Checking Heater Fuse Link Optional Electric HeatersFormulas Refrigeration Repair Practice Leak Testing Nitrogen or NITROGEN-TRACEDEvacuation Brazing MaterialsEvacuation ChargingChecking Compressor Efficiency Final Charge AdjustmentTXV Valves 105B Thermostatic Expansion ValvePressure vs. Temperature Chart 410A Required Liquid Line Temperature Underfeeding OverfeedingSuperheat Checking SubcoolingChecking Expansion Valve Operation 109A TWO Speed ApplicationFixed Orifice Restrictor Devices Subcooling Formula = Sat. Liquid Temp. Liquid LineOvercharge of Refrigerant Checking Restricted Liquid LineNON-CONDENSABLES Compressor BurnoutRefrigerant Piping Accessories for lines greater than 80 feetLong Line SET Application R-410A Tube SizingInstallation Requirements Initial System Charging AIR Handler External StaticCoil Static Pressure Drop Total External StaticStatic Pressure Drop ALL Fuel System AFE18-60A Control Board Accessories Wiring Diagrams10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF