Goodmans DSX, GSZ, ASZ, SSX, ASX Refrigerant Piping, Long Line SET Application R-410A, Tube Sizing

Page 69

SERVICING

NOTE: At least twelve (12) inches of the suction line immediately out of the compressor stub must be discarded due to burned residue and contaminates.

1.Remove compressor discharge line strainer.

2.Remove the liquid line drier and expansion valve.

3Purge all remaining components with dry nitrogen or carbon dioxide until clean.

4.Install new components including liquid line drier.

5.Braze all joints, leak test, evacuate, and recharge sys- tem.

6.Start up the unit and record the pressure drop across the drier.

7.Continue to run the system for a minimum of twelve (12) hours and recheck the pressure drop across the drier. Pressure drop should not exceed 6 PSIG.

8.Continue to run the system for several days, repeatedly checking pressure drop across the suction line drier. If the pressure drop never exceeds the 6 PSIG, the drier has trapped the contaminants. Remove the suction line drier from the system.

9.If the pressure drop becomes greater, then it must be replaced and steps 5 through 9 repeated until it does not exceed 6 PSIG.

NOTICE: Regardless, the cause for burnout must be deter- mined and corrected before the new compressor is started.

S-120 REFRIGERANT PIPING

The piping of a refrigeration system is very important in relation to system capacity, proper oil return to compressor, pumping rate of compressor and cooling performance of the evaporator.

POE oils maintain a consistent viscosity over a large tem- perature range which aids in the oil return to the compressor; however, there will be some installations which require oil return traps. These installations should be avoided whenever possible, as adding oil traps to the refrigerant lines also increases the opportunity for debris and moisture to be introduced into the system. Avoid long running traps in horizontal suction line.

LONG LINE SET APPLICATION R-410A

This long line set application guideline applies to all AHRI listed R-410A air conditioner and heat pump split system matches of nominal capacity 18,000 to 60,000 Btuh. This guideline will cover installation requirements and additional accessories needed for split system installations where the line set exceeds 80 feet in actual length.

Accessories for lines greater than 80 feet:

1.Crankcase Heater- a long line set application can critically increase the charge level needed for a system. As a result, the system is very prone to refrigerant migration during its off-cycle and a crankcase heater will help minimize this risk. A crankcase heater is required for any long line application (50 watt minimum).

2.For all line set applications over 80 feet a TXV is recom- mended. The subcooling should be 6º ± 2º.

3.Hard Start Assist- increased charge level in long line applications can require extra work from the compressor at start-up. A hard start assist device may be required to overcome this.

4.Liquid Line Solenoid - a long line set application can critically increase the charge level needed for a system. As a result, the system is very prone to refrigerant migration during its off-cycle and a liquid line solenoid will help minimize this. A liquid line solenoid is recom- mended for any long line application on straight cooling units.

Tube Sizing:

1.In long line applications, the “equivalent line length” is the sum of the straight length portions of the suction line plus losses (in equivalent length) from 45 and 90 degree bends. Select the proper suction tube size based on equivalent length of the suction line (see Tables 4 & 5) and recalculated system capacity.

Equivalent length =

Length horizontal

+Length vertical

+Losses from bends (see Tables 4 & 5)

Example using ¾” elbow:

150 feet of straight tubing + (four short radius elbows x 1.7) + (2 long radius elbows x 1.5) = 150 + 3.4 +3 =

156.4equivalent feet.

2.For any residential split system installed with a long line set, 3/8" liquid line size must be used. Limiting the liquid line size to 3/8" is critical since an increased refrigerant charge level from having a larger liquid line could possibly shorten a compressor’s life-span.

3.Single Stage Condensing Unit: The maximum length of tubing must not exceed 150 feet.

80 feet is the maximum recommended vertical difference between the condenser and evaporator when the evapo- rator is above the condenser. Equivalent length is not to exceed 150 feet.

•Theverticaldifferencebetweenthecondenserandevapo- rator when the evaporator is below the condenser can approach 150 feet, as long as the equivalent length does not exceed 150 feet.

•The distance between the condenser and evaporator in a completely horizontal installation in which the indoor and outdoor unit do not differ more than 10 feet in vertical distance from each other can approach 150 feet, as long as the equivalent length does not exceed 150 feet.

69

Image 69
Contents Service Instructions Email us at customerservice@goodmanmfg.com Recognize Safety SYMBOLS, Words and LabelsImportant Information Fax us at 713 Fax us at 931 438Safe Refrigerant Handling Split System Heat Pumps R410A Product IdentificationModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 ASX13 AccessoriesDSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Condensing Unit Product DesignFigure a Capacity Control Heating System OperationCooling Cooling CycleHeating Cycle Defrost CycleCooling Cycle System Operation Description AFE18-60A Control BoardCOOLING/HP Analysis Chart Troubleshooting Chart61B ServicingChecking THERMOSTAT, WIRING, and Anticipator Checking Wiring3A Thermostat and Wiring Checking Voltage3C Heating Anticipator 3B Cooling AnticipatorTesting Coil Circuit Checking Time Delay RelayChecking Transformer Control Circuit Checking Cycle ProtectorSingle Phase Testing Compressor ContactorChecking Contactor AND/OR Relays Checking Contactor ContactsTesting FAN Relay Copeland Comfort Alert DiagnosticsDiagnostics Table Checking High Pressure Control Checking Loss of Charge ProtectorChecking LOW Pressure Control Checking Capacitor15A Resistance Check 15B Capacitance CheckRELAY, Start 16B Checking FAN and Blower Motor ECM Motors 16A Checking FAN and Blower Motor Windings PSC MotorsChart on Next Chart from Previous 16C Checking ECM Motor Windings 16D ECM CFM Adjustments MBE / AepfCFM 16E Blower Performance Data 16F Checking GE X13TM MotorsGE X13TM Motor Connections Checking Compressor Testing Compressor Windings17A Resistance Test 17B Ground TestUnloader Test Procedure 17C Unloader Test Procedure17D Operation Test Compressor Ground TestTesting Defrost Control Testing Crankcase Heater Optional ItemTesting Defrost Thermostat Checking Reversing Valve and SolenoidChecking Heater Limit Controls 40 MBR/AR*F Electronic Blower Time Delay RelayChecking Heater Elements Sequence of OperationHeating Operation MBR/AR*F with Single Stage Heat Pumps41 MBE/AEPF with GSX, SSX, ASX, DSX Defrost OperationMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps MBE/AEPF with TWO Stage ASX & DSX Condensers Sequence of OperationMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item 61A Checking Heater Limit Controls 61B Checking Heater Fuse Link Optional Electric HeatersFormulas Refrigeration Repair Practice Leak Testing Nitrogen or NITROGEN-TRACEDEvacuation Brazing MaterialsEvacuation ChargingChecking Compressor Efficiency Final Charge AdjustmentTXV Valves 105B Thermostatic Expansion ValvePressure vs. Temperature Chart 410A Required Liquid Line Temperature Underfeeding OverfeedingSuperheat Checking SubcoolingChecking Expansion Valve Operation 109A TWO Speed ApplicationFixed Orifice Restrictor Devices Subcooling Formula = Sat. Liquid Temp. Liquid LineOvercharge of Refrigerant Checking Restricted Liquid LineNON-CONDENSABLES Compressor BurnoutRefrigerant Piping Accessories for lines greater than 80 feetLong Line SET Application R-410A Tube SizingInstallation Requirements Initial System Charging AIR Handler External StaticCoil Static Pressure Drop Total External StaticStatic Pressure Drop ALL Fuel System AFE18-60A Control Board Accessories Wiring Diagrams10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF