Goodmans ASZ, GSZ, SSX, ASX, DSZ Checking Loss of Charge Protector, Checking High Pressure Control

Page 41

SERVICING

S-11 CHECKING LOSS OF CHARGE PROTECTOR

(Heat Pump Models)

The loss of charge protector senses the pressure in the liquid line and will open its contacts on a drop in pressure. The low pressure control will automatically reset itself with a rise in pressure.

The low pressure control is designed to cut-out (open) at approximately 21 PSIG. It will automatically cut-in (close) at approximately 50 PSIG.

Test for continuity using a VOM and if not as above, replace the control.

S-12 CHECKING HIGH PRESSURE CONTROL

If it cuts-out at 610 PSIG ± 10 PSIG, it is operating normally (See causes for high head pressure in Service Problem Analysis Guide). If it cuts out below this pressure range, replace the control.

HIGH VOLTAGE!

Disconnect ALL power before servicing or installing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

The high pressure control capillary senses the pressure in the compressor discharge line. If abnormally high condensing pressures develop, the contacts of the control open, breaking the control circuit before the compressor motor overloads. This control is automatically reset.

1.Using an ohmmeter, check across terminals of high pressure control, with wire removed. If not continuous, the contacts are open.

3.Attach a gauge to the dill valve port on the base valve. With power ON:

WARNING

Line Voltage now present.

4.Start the system and place a piece of cardboard in front of the condenser coil, raising the condensing pressure.

5.Check pressure at which the high pressure control cuts- out.

S-13 CHECKING LOW PRESSURE CONTROL

The low pressure control senses the pressure in the suction line and will open its contacts on a drop in pressure. The low pressure control will automatically reset itself with a rise in pressure.

The low pressure control is designed to cut-out (open) at approximately 21 PSIG. It will automatically cut-in (close) at approximately 50 PSIG.

Test for continuity using a VOM and if not as above, replace the control.

S-15 CHECKING CAPACITOR

CAPACITOR, RUN

A run capacitor is wired across the auxiliary and main windings of a single phase permanent split capacitor motor. The capacitors primary function is to reduce the line current while greatly improving the torque characteristics of a motor. This is accomplished by using the 90° phase relationship between the capacitor current and voltage in conjunction with the motor windings, so that the motor will give two phase operation when connected to a single phase circuit. The capacitor also reduces the line current to the motor by improving the power factor.

The line side of this capacitor is marked with "COM" and is wired to the line side of the circuit.

CAPACITOR, START

SCROLL COMPRESSOR MODELS

In most cases hard start components are not required on Scroll compressor equipped units due to a non-replaceable check valve located in the discharge line of the compressor. However, in installations that encounter low lock rotor volt- age, a hard start kit can improve starting characteristics and reduce light dimming within the home. Only hard start kits approved by Amana® brand or Copeland should be used. "Kick Start" and/or "Super Boost" kits are not approved start assist devices.

41

Image 41
Contents Service Instructions Email us at customerservice@goodmanmfg.com Recognize Safety SYMBOLS, Words and LabelsImportant Information Fax us at 713 Fax us at 931 438Safe Refrigerant Handling Split System Heat Pumps R410A Product IdentificationModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 ASX13 AccessoriesDSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Condensing Unit Product DesignFigure a Capacity Control Heating System OperationCooling Cooling CycleHeating Cycle Defrost CycleCooling Cycle System Operation Description AFE18-60A Control BoardCOOLING/HP Analysis Chart Troubleshooting Chart61B ServicingChecking THERMOSTAT, WIRING, and Anticipator Checking Wiring3A Thermostat and Wiring Checking Voltage3C Heating Anticipator 3B Cooling AnticipatorTesting Coil Circuit Checking Time Delay RelayChecking Transformer Control Circuit Checking Cycle ProtectorSingle Phase Testing Compressor ContactorChecking Contactor AND/OR Relays Checking Contactor ContactsTesting FAN Relay Copeland Comfort Alert DiagnosticsDiagnostics Table Checking High Pressure Control Checking Loss of Charge ProtectorChecking LOW Pressure Control Checking CapacitorRELAY, Start 15A Resistance Check15B Capacitance Check 16B Checking FAN and Blower Motor ECM Motors 16A Checking FAN and Blower Motor Windings PSC MotorsChart on Next Chart from Previous 16C Checking ECM Motor Windings 16D ECM CFM Adjustments MBE / AepfCFM GE X13TM Motor Connections 16E Blower Performance Data16F Checking GE X13TM Motors Checking Compressor Testing Compressor Windings17A Resistance Test 17B Ground TestUnloader Test Procedure 17C Unloader Test Procedure17D Operation Test Compressor Ground TestTesting Defrost Control Testing Crankcase Heater Optional ItemTesting Defrost Thermostat Checking Reversing Valve and SolenoidChecking Heater Limit Controls 40 MBR/AR*F Electronic Blower Time Delay RelayChecking Heater Elements Sequence of OperationHeating Operation MBR/AR*F with Single Stage Heat PumpsMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41 MBE/AEPF with GSX, SSX, ASX, DSXDefrost Operation 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps MBE/AEPF with TWO Stage ASX & DSX Condensers Sequence of OperationMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item Formulas 61A Checking Heater Limit Controls61B Checking Heater Fuse Link Optional Electric Heaters Refrigeration Repair Practice Leak Testing Nitrogen or NITROGEN-TRACEDEvacuation Brazing MaterialsEvacuation ChargingChecking Compressor Efficiency Final Charge AdjustmentTXV Valves 105B Thermostatic Expansion ValvePressure vs. Temperature Chart 410A Required Liquid Line Temperature Underfeeding OverfeedingSuperheat Checking SubcoolingChecking Expansion Valve Operation 109A TWO Speed ApplicationFixed Orifice Restrictor Devices Subcooling Formula = Sat. Liquid Temp. Liquid LineOvercharge of Refrigerant Checking Restricted Liquid LineNON-CONDENSABLES Compressor BurnoutRefrigerant Piping Accessories for lines greater than 80 feetLong Line SET Application R-410A Tube SizingInstallation Requirements Initial System Charging AIR Handler External StaticStatic Pressure Drop Coil Static Pressure DropTotal External Static ALL Fuel System AFE18-60A Control Board Accessories Wiring Diagrams10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF