Goodmans DSZ, GSZ, ASZ, SSX, ASX, DSX, GSX, SSZ manual 3B Cooling Anticipator, 3C Heating Anticipator

Page 36

SERVICING

4.Check the continuity of the thermostat and wiring. Repair or replace as necessary.

ResistanceHeaters

1.Set room thermostat to a higher setting than room temperature so both stages call for heat.

2.With voltmeter, check for 24 volts at each heater relay. Note: BBA/BBC heater relays are DC voltage.

3.No voltage indicates the trouble is in the thermostat or wiring.

4.Check the continuity of the thermostat and wiring. Repair or replace as necessary.

NOTE: Consideration must be given to how the heaters are wired (O.D.T. and etc.). Also safety devices must be checked for continuity.

S-3B COOLING ANTICIPATOR

The cooling anticipator is a small heater (resistor) in the thermostat. During the "off" cycle, it heats the bimetal

element helping the thermostat call for the next cooling cycle. This prevents the room temperature from rising too high before the system is restarted. A properly sized anticipator should maintain room temperature within 1 1/2 to 2 degree range.

The anticipator is supplied in the thermostat and is not to be replaced. If the anticipator should fail for any reason, the thermostat must be changed.

S-3C HEATING ANTICIPATOR

The heating anticipator is a wire wound adjustable heater which is energized during the "ON" cycle to help prevent overheating of the conditioned space.

The anticipator is a part of the thermostat and if it should fail for any reason, the thermostat must be replaced. See the following tables for recommended heater anticipator setting in accordance to the number of electric heaters installed.

S-3D TROUBLESHOOTING ENCODED TWO STAGE COOLING THERMOSTATS OPTIONS

Troubleshooting Encoded Two Stage Cooling Thermostats Options

T

E

S

T

INPUT

FROM

THERMOSTAT

POWER

TO

THERMOSTAT

TEST

FUNCTION

SIGNAL OUT

SIGNAL FAN

INDICATION

 

 

 

S1 +

LOW SPEED COOL

YCON +

Y1

 

 

 

 

* S1 - *

* LO SPEED COOL *

* YCON - *

* Y / Y2 HI *

 

 

 

 

S1 + -

HI SPEED COOL

YCON + -

Y / Y2

S2 +

LO SPEED HEAT

W1 HEATER

W / W1

 

 

 

 

S2 -

O

ED -

O

 

 

( FUTURE USE )

 

 

 

 

 

S2 + -

LO SPEED HEAT

W1 HEATER

W / W1

 

HI SPEED HEAT

W2 HEATER

EM / W2

 

 

 

 

S3 +

G

NONE

G

 

 

 

 

* S3 - *

N/A

N/A

N/A

* S3 + - *

N/A

N/A

N/A

 

 

 

 

R + -

24 VAC

R TO T'STAT

R

COM

GND

COM TO T'STAT

C1 , C2

 

 

 

 

*ERROR CONDITION ( DIODE ON THERMOSTAT BACKWARDS )

SEE NOTE 3

SEE NOTE 3

*ERROR CONDITION ( S3 CAN ONLY READ + )

*ERROR CONDITION ( S3 CAN ONLY READ + )

NOTES:

1.) THE TEST SPADE CAN BE CONNECTED TO ANY OTHER TEST SPADE ON EITHER BOARD.

2.) THE + LED WILL BE RED AND WILL LIGHT TO INDICATE + HALF CYCLES. THE - LED WILL BE GREEN AND WILL LIGHT TO INDICATE - HALF CYCLES.

BOTH RED AND GREEN ILLUMINATED WILL INDICATE FULL CYCLES DENOTED BY + - .

3.) SIGNAL OUT CONDITION FOR W1 , W2 HEATER WILL BE AFFECTED BY OT1 PJ4 AND OT2 PJ2 JUMPERS AND OUTDOOR THERMOSTATS ATTACHED. THE TABLE ABOVE ASSUMES OT1 PJ4 IS REMOVED AND OT2 PJ2 IS MADE WITH NO OUTDOOR THERMOSTATS ATTACHED.

The chart above provides troubleshooting for either version of the encoded thermostat option. This provides diagnostic information for the GMC CHET18-60 or a conventional two cool / two stage heat thermostat with IN4005 diodes added as called out in the above section.

A test lead or jumper wire can be added from the test terminal to any terminal on the B13682-74 or B13682-71 variable speed terminal board and provide information through the use of the LED lights on the B13682-71 VSTB control. Using this chart, a technician can determine if the proper input signal is being received by the encoded VSTB control and diagnose any problems that may be relayed to the output response of the B13682-74 VSTM control.

36

Image 36
Contents Service Instructions Recognize Safety SYMBOLS, Words and Labels Email us at customerservice@goodmanmfg.comImportant Information Fax us at 713 Fax us at 931 438Safe Refrigerant Handling Product Identification Split System Heat Pumps R410AModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 Accessories ASX13DSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Product Design Condensing UnitFigure a Capacity Control System Operation HeatingCooling Cooling CycleDefrost Cycle Heating CycleCooling Cycle System Operation AFE18-60A Control Board DescriptionTroubleshooting Chart COOLING/HP Analysis ChartServicing 61BChecking Wiring Checking THERMOSTAT, WIRING, and Anticipator3A Thermostat and Wiring Checking Voltage3B Cooling Anticipator 3C Heating AnticipatorChecking Time Delay Relay Testing Coil CircuitChecking Transformer Control Circuit Checking Cycle ProtectorTesting Compressor Contactor Single PhaseChecking Contactor AND/OR Relays Checking Contactor ContactsCopeland Comfort Alert Diagnostics Testing FAN RelayDiagnostics Table Checking Loss of Charge Protector Checking High Pressure ControlChecking LOW Pressure Control Checking Capacitor15A Resistance Check 15B Capacitance CheckRELAY, Start 16A Checking FAN and Blower Motor Windings PSC Motors 16B Checking FAN and Blower Motor ECM MotorsChart on Next Chart from Previous 16D ECM CFM Adjustments MBE / Aepf 16C Checking ECM Motor WindingsCFM 16E Blower Performance Data 16F Checking GE X13TM MotorsGE X13TM Motor Connections Testing Compressor Windings Checking Compressor17A Resistance Test 17B Ground Test17C Unloader Test Procedure Unloader Test Procedure17D Operation Test Compressor Ground TestTesting Crankcase Heater Optional Item Testing Defrost ControlTesting Defrost Thermostat Checking Reversing Valve and Solenoid40 MBR/AR*F Electronic Blower Time Delay Relay Checking Heater Limit ControlsChecking Heater Elements Sequence of OperationMBR/AR*F with Single Stage Heat Pumps Heating Operation41 MBE/AEPF with GSX, SSX, ASX, DSX Defrost OperationMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps Sequence of Operation MBE/AEPF with TWO Stage ASX & DSX CondensersMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item 61A Checking Heater Limit Controls 61B Checking Heater Fuse Link Optional Electric HeatersFormulas Leak Testing Nitrogen or NITROGEN-TRACED Refrigeration Repair PracticeEvacuation Brazing MaterialsCharging EvacuationFinal Charge Adjustment Checking Compressor Efficiency105B Thermostatic Expansion Valve TXV ValvesPressure vs. Temperature Chart 410A Required Liquid Line Temperature Overfeeding UnderfeedingSuperheat Checking Subcooling109A TWO Speed Application Checking Expansion Valve OperationFixed Orifice Restrictor Devices Subcooling Formula = Sat. Liquid Temp. Liquid LineChecking Restricted Liquid Line Overcharge of RefrigerantNON-CONDENSABLES Compressor BurnoutAccessories for lines greater than 80 feet Refrigerant PipingLong Line SET Application R-410A Tube SizingInstallation Requirements AIR Handler External Static Initial System ChargingCoil Static Pressure Drop Total External StaticStatic Pressure Drop Accessories Wiring Diagrams ALL Fuel System AFE18-60A Control Board10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF