SERVICING
S-106 OVERFEEDING
Overfeeding by the expansion valve results in high suction pressure, cold suction line, and possible liquid slugging of the compressor.
If these symptoms are observed:
1.Check for an overcharged unit by referring to the cooling performance charts in the servicing section.
2.Check the operation of the power element in the valve as explained in
3.Check for restricted or plugged equalizer tube.
S-107 UNDERFEEDING
Underfeeding by the expansion valve results in low system capacity and low suction pressures.
If these symptoms are observed:
1.Check for a restricted liquid line or drier. A restriction will be indicated by a temperature drop across the drier.
2.Check the operation of the power element of the valve as described in
S-108 SUPERHEAT
The expansion valves are factory adjusted to maintain 8 to 12 degrees superheat of the suction gas. Before checking the superheat or replacing the valve, perform all the procedures outlined under Air Flow, Refrigerant Charge, Expansion Valve
-Overfeeding, Underfeeding. These are the most common causes for evaporator malfunction.
CHECKINGSUPERHEAT
Refrigerant gas is considered superheated when its tempera- ture is higher than the saturation temperature corresponding to its pressure. The degree of superheat equals the degrees of temperature increase above the saturation temperature at existing pressure. See Temperature - Pressure Chart on following pages.
CAUTION
To prevent personal injury, carefully connect and disconnect manifold gauge hoses. Escaping liquid refrigerant can cause burns. Do not vent refrigerant to atmosphere. Recover during system repair
or final unit disposal.
1.Run system at least 10 minutes to allow pressure to stabilize.
2.Temporarily install thermometer on suction (large) line near suction line service valve with adequate contact and insulate for best possible reading.
3.Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat.
Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp.
EXAMPLE:
a.Suction Pressure = 143
b.Corresponding Temp. °F. = 50
c.Thermometer on Suction Line = 61°F.
To obtain the degrees temperature of superheat, subtract 50.0 from 61.0°F.
The difference is 11° Superheat. The 11° Superheat would fall in the ± range of allowable superheat.
SUPERHEAT AND SUBCOOLING ADJUSTMENT ON TXV APPLICATIONS
1.Run system at least 10 minutes to allow pressure to stabilize.
2.Temporarily install thermometer on liquid (small) line near liquid line service valve with adequate contact and insulate for best possible reading.
3.Check subcooling and superheat. Systems with TXV application should have a subcooling and superheat of 7 ± 2ºF.
a.If subcooling and superheat are low, adjust TXV to 7 - 9ºF then check subcooling.
b.If subcooling is low and superheat is high, add charge to raise subcooling to 7 ± 2ºF then check superheat.
c.If subcooling and superheat are high, adjust TXV valve to 7 ± 9ºF then check subcooling.
d.If subcooling is high and superheat is low, adjust TXV valve to 7 to 9ºF superheat and remove charge to lower the subcooling to 7 ± 2ºF.
The TXV should NOT be adjusted at light load conditions 55º to 60ºF, under such conditions only the subcooling can be evaluated. This is because suction pressure is dependent on the indoor coil match, indoor airflow, and wet bulb temperature. NOTE: Do NOT adjust charge based on suction pressure unless there is a gross undercharge.
4. Disconnect manifold set. Installation is complete.
S-109 CHECKING SUBCOOLING
Refrigerant liquid is considered subcooled when its tempera- ture is lower than the saturation temperature corresponding to its pressure. The degree of subcooling equals the degrees of temperature decrease below the saturation temperature at the existing pressure.
1.Attach an accurate thermometer or preferably a thermo- couple type temperature tester to the liquid line as it leaves the condensing unit.
2.Install a high side pressure gauge on the high side (liquid) service valve at the front of the unit.
3.Record the gauge pressure and the temperature of the line.
66