SERVICING
Cooling/Heat Pump Operation
Model | Switch 5 | Switch 6 | CFM | |
| OFF | OFF | 1,200 | |
MBE1200 | ON | OFF | 1,000 | |
OFF | ON | 800 | ||
| ||||
| ON | ON | 600 | |
| OFF | OFF | 1,600 | |
MBE1600 | ON | OFF | 1,400 | |
OFF | ON | 1,200 | ||
| ||||
| ON | ON | 1,000 | |
| OFF | OFF | 2,000 | |
MBE2000 | ON | OFF | 1,800 | |
OFF | ON | 1,600 | ||
| ||||
| ON | ON | 1,200 |
Table 3
THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 30% of the cooling setting.
CFM TRIM ADJUST
Minor adjustments can be made through the dip switch combination of
NOTE: The airflow will not make the decreasing adjustment in Electric Heat mode.
| CFM | S w itc h 7 | S w itc h 8 |
| + 1 0 % | O N | O F F |
| O F F | O N | |
|
| Table 4 |
|
HUMIDITY CONTROL |
|
|
When using a Humidstat (normally closed), cut jumper PJ6 on the control board. The Humidstat will only affect cooling airflow by adjusting the Airflow to 85%.
TWO STAGE HEATING
When using staged electric heat, cut jumper PJ4 on the control board.
AEPF DIPSWITCH FUNCTIONS
Dipswitch 1/2 & 7/8 |
|
|
|
|
|
|
|
|
|
|
| ||||||
AEPF 1830 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Heating |
| Switch | Switch |
| Emergency |
| Heat Pump | ||||||||||
Element |
| Position | Position |
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| Backup |
| With Backup | |||
| (kw) |
| 1 |
|
| 2 | 7 | 8 |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
UP TO 10 |
| OFF |
| OFF | OFF |
| OFF |
| 1100 |
|
| 1210 |
| ||||
UP TO 10 |
| ON |
| OFF | OFF |
| OFF |
| 890 |
|
| 935 |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
|
| OFF |
| ON | OFF |
| OFF |
| 700 |
|
| 770 |
| |||
AEPF3036 / 3137 / 4260 |
|
|
|
|
|
|
|
|
|
|
| ||||||
Heating |
| Switch | Switch |
| Emergency |
| Heat Pump | ||||||||||
Element |
| Position | Position |
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| Backup |
| With Backup | |||
| (kw) |
| 1 |
|
| 2 | 7 | 8 |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
UP TO 20 |
| OFF |
| OFF | OFF |
| OFF |
| 2050 |
|
| 2150 |
| ||||
UP TO 20 |
| ON |
| OFF | OFF |
| OFF |
| 1750 |
|
| 1835 |
| ||||
UP TO 15 |
| OFF |
| ON | OFF |
| OFF |
| 1600 |
|
| 1680 |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UP TO 10 |
| ON |
| ON | OFF |
| OFF |
| 1200 |
|
| 1260 |
| ||||
UP TO 10 |
| ON |
| ON | OFF |
| ON |
| 1020 |
|
| 1070 |
| ||||
| Dipswitch 5/6 & 7/8 |
|
|
|
|
|
|
|
|
|
| ||||||
| AEPF 1830 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Switch |
|
| Switch |
|
|
| Indoor Airflow |
| ||||||||
| Position |
|
| Position |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
| 5 |
| 6 |
|
| 7 | 8 |
| Cooling |
| Heat Pump |
| |||||
| OFF |
| OFF |
|
| OFF | OFF |
|
| 1100 |
|
| 1100 |
| |||
| ON |
| OFF |
|
| OFF | OFF |
|
| 800 |
|
| 800 |
| |||
| OFF |
|
| ON |
|
| OFF | OFF |
|
| 600 |
|
| 600 |
| ||
| AEPF3036 / 3137 / 4260 |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Switch |
|
| Switch |
|
|
| Indoor Airflow |
| ||||||||
| Position |
|
| Position |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |||||||
| 5 |
| 6 |
|
| 7 | 8 |
| Cooling |
| Heat Pump |
| |||||
| OFF |
| OFF |
|
| OFF | OFF |
|
| 1800 |
|
| 1800 |
| |||
| ON |
| OFF |
|
| OFF | OFF |
|
| 1580 |
|
| 1580 |
| |||
| OFF |
|
| ON |
|
| OFF | OFF |
|
| 1480 |
|
| 1480 |
| ||
| ON |
|
| ON |
|
| OFF | OFF |
|
| 1200 |
|
| 1200 |
| ||
| ON |
|
| ON |
|
| OFF | ON |
|
| 1020 |
|
| 1020 |
|
47