Goodmans DSZ, GSZ Checking Restricted Liquid Line, Overcharge of Refrigerant, Non-Condensables

Page 68

SERVICING

2.Remove the orifice or tube strainer assembly and re- place.

3.Replace liquid line drier, evacuate and recharge.

CHECKING EQUALIZATION TIME

During the "OFF" cycle, the high side pressure bleeds to the low side through the fixed orifice restriction device. Check equalization time as follows:

1.Attach a gauge manifold to the suction and liquid line dill valves.

2.Start the system and allow the pressures to stabilize.

3.Stop the system and check the time it takes for the high and low pressure gauge readings to equalize.

If it takes more than seven (7) minutes to equalize, the restrictor device is inoperative. Replace, install a liquid line drier, evacuate and recharge.

S-112 CHECKING RESTRICTED LIQUID LINE

When the system is operating, the liquid line is warm to the touch. If the liquid line is restricted, a definite temperature drop will be noticed at the point of restriction. In severe cases, frost will form at the restriction and extend down the line in the direction of the flow.

Discharge and suction pressures will be low, giving the appearance of an undercharged unit. However, the unit will have normal to high subcooling.

Locate the restriction, replace the restricted part, replace drier, evacuate and recharge.

S-113 OVERCHARGE OF REFRIGERANT

An overcharge of refrigerant is normally indicated by an excessively high head pressure.

An evaporator coil, using an expansion valve metering device, will basically modulate and control a flooded evaporator and prevent liquid return to the compressor.

An evaporator coil, using a capillary tube metering device, could allow refrigerant to return to the compressor under extreme overcharge conditions. Also with a capillary tube metering device, extreme cases of insufficient indoor air can cause icing of the indoor coil and liquid return to the compressor, but the head pressure would be lower.

There are other causes for high head pressure which may be found in the "Service Problem Analysis Guide."

If other causes check out normal, an overcharge or a system containing non-condensables would be indicated.

If this system is observed:

1.Start the system.

2.Remove and capture small quantities of gas from the suction line dill valve until the head pressure is reduced to normal.

3.Observe the system while running a cooling performance test. If a shortage of refrigerant is indicated, then the system contains non-condensables.

S-114 NON-CONDENSABLES

If non-condensables are suspected, shut down the system and allow the pressures to equalize. Wait at least 15 minutes. Compare the pressure to the temperature of the coldest coil since this is where most of the refrigerant will be. If the pressure indicates a higher temperature than that of the coil temperature, non-condensables are present.

Non-condensables are removed from the system by first removing the refrigerant charge, replacing and/or installing liquid line drier, evacuating and recharging.

S-115 COMPRESSOR BURNOUT

When a compressor burns out, high temperature develops causing the refrigerant, oil and motor insulation to decom- pose forming acids and sludge.

If a compressor is suspected of being burned-out, attach a refrigerant hose to the liquid line dill valve and properly remove and dispose of the refrigerant.

NOTICE

Violation of EPA regulations may result in fines or other penalties.

Now determine if a burn out has actually occurred. Confirm by analyzing an oil sample using a Sporlan Acid Test Kit, AK- 3 or its equivalent.

Remove the compressor and obtain an oil sample from the suction stub. If the oil is not acidic, either a burnout has not occurred or the burnout is so mild that a complete clean-up is not necessary.

If acid level is unacceptable, the system must be cleaned by using the clean-up drier method.

CAUTION

Do not allow the sludge or oil to contact the skin. Severe burns may result.

NOTE: The Flushing Method using R-11 refrigerant is no longer approved by Amana® Brand Heating-Cooling.

Suction Line Drier Clean-Up Method

The POE oils used with R410A refrigerant is an excellent solvent. In the case of a burnout, the POE oils will remove any burnout residue left in the system. If not captured by the refrigerant filter, they will collect in the compressor or other system components, causing a failure of the replacement compressor and/or spread contaminants throughout the system, damaging additional components.

Use AMANA® brand part number RF000127 suction line filter drier kit. This drier should be installed as close to the compressor suction fitting as possible. The filter must be accessible and be rechecked for a pressure drop after the system has operated for a time. It may be necessary to use new tubing and form as required.

68

Image 68
Contents Service Instructions Recognize Safety SYMBOLS, Words and Labels Email us at customerservice@goodmanmfg.comImportant Information Fax us at 713 Fax us at 931 438Safe Refrigerant Handling Product Identification Split System Heat Pumps R410AModel # Description Split System Air Conditioners R410A ASX130**1AA Single Piece Air Handlers AWUF****1AA MBR/MBE Air Handlers Product Identification 1824 3642 Accessories ASX13DSX/SSX16 ASX18 ASZ13 DSZ/SSZ16 ASZ18 Expansion Valve Kits FSK01A Coil Accessories Electric Heat Kitapplications Aruf Electric Heat Kitapplications Aepf Product Design Condensing UnitFigure a Capacity Control System Operation HeatingCooling Cooling CycleDefrost Cycle Heating CycleCooling Cycle System Operation AFE18-60A Control Board DescriptionTroubleshooting Chart COOLING/HP Analysis ChartServicing 61BChecking Wiring Checking THERMOSTAT, WIRING, and Anticipator3A Thermostat and Wiring Checking Voltage3B Cooling Anticipator 3C Heating AnticipatorChecking Time Delay Relay Testing Coil CircuitChecking Transformer Control Circuit Checking Cycle ProtectorTesting Compressor Contactor Single PhaseChecking Contactor AND/OR Relays Checking Contactor ContactsCopeland Comfort Alert Diagnostics Testing FAN RelayDiagnostics Table Checking Loss of Charge Protector Checking High Pressure ControlChecking LOW Pressure Control Checking CapacitorRELAY, Start 15A Resistance Check15B Capacitance Check 16A Checking FAN and Blower Motor Windings PSC Motors 16B Checking FAN and Blower Motor ECM MotorsChart on Next Chart from Previous 16D ECM CFM Adjustments MBE / Aepf 16C Checking ECM Motor WindingsCFM GE X13TM Motor Connections 16E Blower Performance Data16F Checking GE X13TM Motors Testing Compressor Windings Checking Compressor17A Resistance Test 17B Ground Test17C Unloader Test Procedure Unloader Test Procedure17D Operation Test Compressor Ground TestTesting Crankcase Heater Optional Item Testing Defrost ControlTesting Defrost Thermostat Checking Reversing Valve and Solenoid40 MBR/AR*F Electronic Blower Time Delay Relay Checking Heater Limit ControlsChecking Heater Elements Sequence of OperationMBR/AR*F with Single Stage Heat Pumps Heating OperationMBE/AEPF with Single Stage GSX, ASX and SSX Condensers 41 MBE/AEPF with GSX, SSX, ASX, DSXDefrost Operation 41A MBE/AEPF with Single Stage GSZ, SSZ, & ASZ Heat Pumps Sequence of Operation MBE/AEPF with TWO Stage ASX & DSX CondensersMBE/AEPF with TWO Stage ASZ & DSZ Heat Pump Units Electric Heater Optional Item Formulas 61A Checking Heater Limit Controls61B Checking Heater Fuse Link Optional Electric Heaters Leak Testing Nitrogen or NITROGEN-TRACED Refrigeration Repair PracticeEvacuation Brazing MaterialsCharging EvacuationFinal Charge Adjustment Checking Compressor Efficiency105B Thermostatic Expansion Valve TXV ValvesPressure vs. Temperature Chart 410A Required Liquid Line Temperature Overfeeding UnderfeedingSuperheat Checking Subcooling109A TWO Speed Application Checking Expansion Valve OperationFixed Orifice Restrictor Devices Subcooling Formula = Sat. Liquid Temp. Liquid LineChecking Restricted Liquid Line Overcharge of RefrigerantNON-CONDENSABLES Compressor BurnoutAccessories for lines greater than 80 feet Refrigerant PipingLong Line SET Application R-410A Tube SizingInstallation Requirements AIR Handler External Static Initial System ChargingStatic Pressure Drop Coil Static Pressure DropTotal External Static Accessories Wiring Diagrams ALL Fuel System AFE18-60A Control Board10kw and Below, One Stage Electric Heat OT/EHR18-60 #2 GRD PLM PLF XFMR-R XFMR-C After Installing Optional Heat KIT, Mark AN X Provided Above HKR Heat Kit GRD PLM PLF