Displaying Metering Information
1.Install the HIM on the
2.Turn on machine power.
3.After three to five seconds of initialization, display will show the status display. If drive is in a faulted condition, fault will appear in display; otherwise, drive will read current status. Refer to examples below.
Faulted Drive | Normal Condition |
6.Press the Enter key to choose Group Level. Display will read:
Choose Group
Metering
For earlier HIM versions, press the Enter key to choose Main File. Display will read:
Metering
Main File
Fault Description Fault Number
Examples of Faults
Serial Fault
F 10
Max Retries Fault F 33
Status of Drive Frequency Commanded
Example of Normal
Condition
Stopped
+0.00 Hz
7.Use the Up and Down arrow keys to select “Metering” if not displayed immediately.
8.Press the Enter key to choose Parameter Level. Display now shows parameters under the “Metering” Group.
Output Current
0.00 Amps |
4. Press any key to enter Mode Level,
ESC SEL
. Display will read:
Choose Mode
Display
5.Use the Up and Down arrow keys to select “Display” if not displayed immediately.
9. | Use the Up and Down arrow keys | to |
| select desired parameter display. |
|
10. | From this point, press the Escape key | ESC to |
| move display up one Level (i.e., press the Escape | |
| key three times to return to Operator Level). |