Table 56 (continued)
| Fault | Description | Corrective Action |
| Remarks | ||
|
|
| |
|
|
|
|
39 | Phase V Fault | Phase to ground fault detected | Check wiring between the drive and motor. Check for |
|
| between controller and motor in | grounded phase. |
|
| Phase V. |
|
|
|
|
|
40 | Phase W Fault | Phase to ground fault detected | Check wiring between the drive and motor. Check for |
|
| between controller and motor in | grounded phase. |
|
| Phase W. |
|
|
|
|
|
41 | UV Short Fault | Excessive current has been | Check motor and external wiring to the controller output |
|
| detected between two controller | terminals for shorted condition. |
|
| output terminals. |
|
|
|
|
|
42 | UW Short Fault | Excessive current has been | Check motor and external wiring to the controller output |
|
| detected between two controller | terminals for shorted condition. |
|
| output terminals. |
|
|
|
|
|
43 | VW Short Fault | Excessive current has been | Check motor and external wiring to the controller output |
|
| detected between two controller | terminals for shorted condition. |
|
| output terminals. |
|
|
|
|
|
57 | Ground Warning | A current path to ground in excess | Check motor and external wiring to drive output terminals |
|
| of 2A has been detected at one or | for a grounded condition. |
|
| more of the drive output terminals. |
|
|
|
|
|
48 | Reset to Default Values | Parameters were reset to the | Verify and |
|
| factory default values. |
|
|
|
|
|
Table 56