Chapter 9 - PowerView Display Messages
| PowerView | Meaning | Corrective Action |
| Message | ||
|
|
| |
|
|
|
|
| #Pwr modules changed | At least one power module has | No corrective action necessary. |
| since last ON. | been added, or removed from | Proceed with the startup. |
|
| the SymmetraTM since the last |
|
|
| time the Pwr ON command |
|
|
| was issued. |
|
|
|
|
|
| #Batteries changed since | At least one battery module | No corrective action necessary. |
| last ON. | has been added, or removed | Proceed with the startup. |
|
| from the SymmetraTM since |
|
|
| the last time the Pwr ON |
|
|
| command was issued. |
|
|
|
|
|
| No Redundant | There is no RIM installed. | Proceed with the startup, or abort |
| Intelligence Module. | Note: This message sometimes | the startup, and install a RIM. |
|
| occurs at powerup because the | Note: Without a functioning RIM, |
|
| MIM detects the RIM before | there is no redundancy in the event |
|
| the RIM is "awake." | of a MIM failure. |
|
|
|
|
| Batt capacity less than | The battery capacity of the | Option #1: Abort the startup, and |
| Return Batt Cap | SymmetraTM is less than the | allow batteries to recharge. |
|
| user specified minimum | Option #2: Continue startup, |
|
| battery capacity required to | with less than minimum battery |
|
| turn on the load. | capacity. |
|
|
|
|
| Input Freq outside | The input frequency to the | Option #1: Improve the |
| configured range | SymmetraTM is outside the | frequency of the incoming voltage. |
|
| configured range. The output | Option #2: Widen the range of |
|
| frequency will not | the acceptable incoming |
|
| synchronize with the input | frequency with the PowerView. |
|
| frequency. Normal bypass is | |
|
| not available. | Option #3: Proceed with startup. |
|
|
| Normal bypass is not available. |
|
|
|
|
| AC adequate for UPS | The SymmetraTM will function | Option #1: Improve the incoming |
| but not for bypass | online with the input voltage, | voltage. |
|
| but in the event that bypass is | Option #2: Proceed with startup. |
|
| required, the input voltage is | Normal bypass is not available. |
|
| not adequate to power the |
|
|
| load equipment. |
|
|
|
|
|
| Low/No AC input, | Input voltage is not adequate | Option #1: Abort startup until |
| startup on battery | to start the SymmetraTM. If | acceptable input voltage is present. |
|
| startup proceeds, SymmetraTM | Option #2: Proceed with startup. |
|
| will function from battery. | Battery will be discharged. |
|
|
|
|