Chapter 9 - PowerView Display Messages

 

PowerView

Meaning

Corrective Action

 

Message

 

 

 

 

 

 

 

Start-Up

#Pwr modules changed

At least one power module has

No corrective action necessary.

 

since last ON.

been added, or removed from

Proceed with the startup.

 

 

the SymmetraTM since the last

 

 

 

time the Pwr ON command

 

 

 

was issued.

 

 

 

 

 

 

#Batteries changed since

At least one battery module

No corrective action necessary.

 

last ON.

has been added, or removed

Proceed with the startup.

 

 

from the SymmetraTM since

 

 

 

the last time the Pwr ON

 

 

 

command was issued.

 

 

 

 

 

 

No Redundant

There is no RIM installed.

Proceed with the startup, or abort

 

Intelligence Module.

Note: This message sometimes

the startup, and install a RIM.

 

 

occurs at powerup because the

Note: Without a functioning RIM,

 

 

MIM detects the RIM before

there is no redundancy in the event

 

 

the RIM is "awake."

of a MIM failure.

 

 

 

 

 

Batt capacity less than

The battery capacity of the

Option #1: Abort the startup, and

 

Return Batt Cap

SymmetraTM is less than the

allow batteries to recharge.

 

 

user specified minimum

Option #2: Continue startup,

 

 

battery capacity required to

with less than minimum battery

 

 

turn on the load.

capacity.

 

 

 

 

 

Input Freq outside

The input frequency to the

Option #1: Improve the

 

configured range

SymmetraTM is outside the

frequency of the incoming voltage.

 

 

configured range. The output

Option #2: Widen the range of

 

 

frequency will not

the acceptable incoming

 

 

synchronize with the input

frequency with the PowerView.

 

 

frequency. Normal bypass is

(Startup-Setup-OutputFreq-Select.)

 

 

not available.

Option #3: Proceed with startup.

 

 

 

Normal bypass is not available.

 

 

 

 

 

AC adequate for UPS

The SymmetraTM will function

Option #1: Improve the incoming

 

but not for bypass

online with the input voltage,

voltage.

 

 

but in the event that bypass is

Option #2: Proceed with startup.

 

 

required, the input voltage is

Normal bypass is not available.

 

 

not adequate to power the

 

 

 

load equipment.

 

 

 

 

 

 

Low/No AC input,

Input voltage is not adequate

Option #1: Abort startup until

 

startup on battery

to start the SymmetraTM. If

acceptable input voltage is present.

 

 

startup proceeds, SymmetraTM

Option #2: Proceed with startup.

 

 

will function from battery.

Battery will be discharged.

 

 

 

 

9-1

Page 65
Image 65
American Power Conversion PX user manual PowerView Meaning Corrective Action Message Start-Up, MIM detects the RIM before