American Power Conversion PX Battery modules are being, Because of a power failure, wait for

Models: PX

1 75
Download 75 pages 23.98 Kb
Page 68
Image 68

Chapter 9 - PowerView Display Messages

 

PowerView

Meaning

Corrective Action

 

Message

 

 

 

 

 

 

 

Bypass

Bypass contactor stuck

SymmetraTM is stuck in the

Call your contract service

 

in on-line position.

on-line position, and cannot

provider, or APC Technical

 

 

go to bypass.

Support. (See inside front cover.)

 

 

 

 

 

UPS in bypass due to

SymmetraTM has transferred to

Call your contract service

 

internal fault.

bypass mode because a fault

provider, or APC Technical

 

 

has occurred.

Support. (See inside front cover.)

 

 

 

 

 

UPS in bypass due to

The load has exceeded the

Option #1: Decrease the load.

 

overload

system power capacity. The

Option #2: If possible, add power

 

 

SymmetraTM has switched to

modules to the system.

 

 

bypass mode.

 

 

 

 

 

 

System is in

The SymmetraTM is in bypass

No corrective action necessary.

 

Maintenance Bypass

because the maintenance

 

 

 

bypass switch is in the "on"

 

 

 

position.

 

 

 

 

 

General

On Battery

The SymmetraTM is in the on

No corrective action necessary.

Fault

 

battery mode of operation.

Note: Runtime is limited in

 

 

The battery modules are being

duration. Prepare to shutdown the

 

 

discharged.

SymmetraTM and the load

 

 

equipment, or restore incoming

 

 

 

 

 

 

voltage.

 

 

 

 

 

Need Bat Replacement

One or more battery modules

Refer to Chapter 8 for module

 

 

are in need of replacement.

replacement procedures.

 

 

 

 

 

UPS Fault

A fault has occurred in a

Call your contract service

 

 

power module. This will

provider, or APC Technical

 

 

always occur with a bad

Support. (See inside front cover.)

 

 

power module failure

 

 

 

message.

 

 

 

 

 

 

Shutdown or unable to

SymmetraTM has shutdown

Option #1: Reduce the load to

 

transfer to Batt due to

because an overload has

eliminate overload.

 

overload

occurred and bypass is not

Option #2: If possible, add power

 

 

available.

modules to eliminate overload.

 

 

 

Option #3: Replace failed power

 

 

 

modules to eliminate overload.

 

 

 

Note: If bypass is not available

 

 

 

because of a power failure, wait for

 

 

 

power to be restored. If there is a

 

 

 

utility problem, have it corrected.

 

 

 

 

 

Load Shutdown from

SymmetraTM has shut the load

Correct the input voltage

 

Bypass. Input Freq/Volts

down while it was on bypass,

problem.

 

outside limits.

because the input power went

 

 

 

out of acceptable range.

 

 

 

 

 

 

Fault, Battery Charger

The battery charger in one or

Refer to Chapter 8 for module

 

Failure

more power module(s) failed.

replacement procedures.

 

 

 

 

 

Fault, Bypass Relay

The bypass relay has

Call your contract service

 

Malfunction

malfunctioned.

provider, or APC Technical

 

 

 

Support. (See inside front cover.)

 

 

 

 

9-4

Page 68
Image 68
American Power Conversion PX user manual Battery modules are being, Because of a power failure, wait for