Chapter 5 - System Setup

q6. Press the“Down” arrow key to scroll to the power mod- ule status screen.

Fig 5-20 Power Module Status Screen

Verfiy the following:

qTotal “Pwr” modules (power modules) reported is the same as the actual number of power modules that are installed.

qBad power modules reported is 00 (zero).

qThe first line of the power module status screen displays the reported capacity of the SymmetraTM. The reported capacity is based on the number of power modules installed and the size of the frame. See table 5-1 to confirm that the PowerView is

reporting the correct information.

q8. Follow these steps to deliver output voltage to the

load equipment. See figure 5-22 for the screen sequence: Note: It is recommended that load equipment be switched “off” while this step is performed. After output voltage is delivered, switch the load equipment “on.”

qPress the “ESC” key until the startup screen appears.

qPress the “Enter” key to display the top level menu.

qPress the“Down”key until the selection arrow points to the “Control” menu item.

qPress the “Enter” key.

qPress the “Down” key, until the selection arrow points to “Turn Load ON.”

qPress the “Enter” key.

qConfirm that you want to turn the load on, by selecting “YES, Turn UPS ON”

qSeveral other over-ride messages may appear, depending on the system configuration. Select“Start Now” for any of these startup over-ride messages.

Power

Reported

Reported

Modules

Capacity in

Capacity in

Installed

MiniFrame

MasterFrame

 

 

 

1

4 kVA

4 kVA

 

 

 

2

8 kVA

8 kVA

 

 

 

3

8 kVA

12 kVA

 

 

 

4

n/a

16 kVA

 

 

 

5

n/a

16 kVA

 

 

 

Table 5-1 SymmetraTM Power Module/Frame Capacities

q7. Press the “Down” arrow key to scroll to the miscella- neous status screen. The bottom line indicates the status of the Main Intelligence Module (MIM) and the Redundant In- telligence Module (•RIM). The sample screen in figure 5-21 indicates that both are installed and functioning properly (OK). If a module is not installed, the status screen will dis- play the word “NONE.” Confirm that the IM and RIM status are correct. Use the “ESC” key to return to the startup screen.

Fig 5-21 Miscellaneous Status Screen

Fig 5-22 Power The Load Sequence

After several seconds, the PowerView display should report that the “UPS LOAD IS ON.” Press the “ESC” key to return to the startup screen. Confirm that output voltage is present and that the Load On LED indicator is glowing.

Note: The Bypass LED indicator may flash on briefly, and the On Battery LED indicator may glow for 20-30 seconds if the system is configured for “self test at power on.”

q9. Perform a self test by following the screen sequence in figure 5-23.

Fig 5-23 Initiate a Self Test Sequence

The On Battery LED indicator should glow for approximately 30 seconds. A message will appear on the display indicating that a self test is in progress. When the “Self Test Complete” message appears, press any key to return to the startup screen.

5-8

Page 44
Image 44
American Power Conversion PX user manual Power Reported, SymmetraTM Power Module/Frame Capacities