Chapter 9 - PowerView Display Messages

 

PowerView

Meaning

Corrective Action

 

Message

 

 

 

 

 

 

 

General

# of batteries increased.

At least one battery module has

No corrective action necessary.

Status

been added to the system.

 

 

 

 

 

 

 

# of batteries decreased.

At least one battery module has

No corrective action necessary.

 

been removed from the system.

 

 

 

 

 

 

 

 

# of Pwr Modules

At least one power module has

No corrective action necessary.

 

increased.

been added to the system.

 

 

 

 

 

 

 

# of Pwr Modules

At least one power module has

No corrective action necessary.

 

decreased.

been removed from the system.

 

 

 

 

 

 

 

Intelligence Module

A MIM has been installed into

No corrective action necessary.

 

inserted.

the SymmetraTM .

 

 

 

 

 

 

 

Intelligence Module

A MIM has been removed from

No corrective action necessary.

 

removed

the SymmetraTM .

 

 

 

 

 

 

 

Redundant Intelligence

A RIM has been installed into the

No corrective action necessary.

 

Module inserted.

SymmetraTM .

 

 

Redundant Intelligemce

A RIM has been removed from

No corrective action necessary.

 

Module removed.

the SymmetraTM .

 

 

 

 

 

 

 

# of External Battery

At least one external battery

 

 

cabinet has been connected to

No corrective action necessary.

 

Cabinets increased.

 

the frame.

 

 

 

 

 

# of External Battery

At least one external battery

 

 

cabinets has been disconnected

No corrective action necessary.

 

Cabinets decreased.

 

from the SymmetraTM.

 

 

 

 

 

 

A loss of power module

 

 

 

redundancy occurred, and has

 

 

Redundancy Restored

been restored. Either additional

No corrective action necessary.

 

 

modules have been installed, or

 

 

 

the load has been reduced.

 

 

 

 

 

 

 

The load had exceeded the load

 

 

Load is No Longer above

alarm threshold. The situation

 

 

has been corrected either because

No corrective action necessary.

 

Alarm Threshold

the load decreased, or the

 

 

 

 

 

 

threshold was increased.

 

 

 

 

 

 

 

The system runtime had dropped

 

 

 

below the configured minimum,

 

 

 

and has been restored. Either

 

 

Min Runtime restored.

additional battery modules were

No corrective action necessary.

 

installed, the existing battery

 

 

 

 

 

modules recharged, the load was

 

 

 

reduced, or the threshold was

 

 

 

raised.

 

 

 

 

 