Chapter 8 - Module Replacement

Main Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array. The intelligence module resides under the redundant intelligence module in the upper right corner of the frame.

Note: If a functioning RIM is installed, it will provide limited control of the SymmetraTM until the replacement MIM is installed. If a functioning RIM is not installed, either the SymmetraTM must be placed in manual bypass mode or the load equipment must be switched off. To place the SymmetraTM in manual bypass, switch the maintenance bypass switch to the “on” position.

Important: When the SymmetraTM is in bypass mode, the load equipment is unprotected from power failure.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the MIM out of the frame.

Installing the Replacement Main Intelligence Module

Refer to Chapter 5 for the MIM installation procedure.

Note: If SymmetraTM was placed in manual bypass in step 1 above, return to normal operation by switching the maintenance bypass switch back to the “off” position.

Replacement MIM Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in figure 8-10 to ensure that the replacement MIM is functioning properly. (Status: On & OK).

Fig 8-10 Intelligence Module Verification

Redundant Intelligence Module Replacement

1.Remove the grill cover from the top level of the Power Array. The redundant intelligence module resides above the intelligence module in the upper right corner of the frame.

Note. A RIM can only be replaced if a functioning MIM is in- stalled or the load equipment is switched off.

2.Use a flathead screwdriver to release the flip latch.

3.Unscrew and release the retaining screws.

4.Slide the RIM out of the frame.

Installing the Replacement Redundant Intelligence Module

Refer to Chapter 5 for the RIM installation procedure.

Note: A RIM alone is not adequate to restart the SymmetraTM. Make sure a functioning MIM is installed.

Replacement Redundant Intelligene Module Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in figure 8-11 to ensure that the replacement RIM is functioning properly. (Status: On & OK).

Fig 8-11 Redundant Intelligence Module Verification

8-4

Page 63
Image 63