Chapter 9 - PowerView Display Messages

 

PowerView

Meaning

Corrective Action

 

Message

 

 

 

 

 

 

 

Module

Bad Battery Module

A battery module has failed,

Refer to Chapter 8 for module

Failure

and requires replacement.

replacement procedure.

 

 

 

 

 

 

Bad Power Module

A power module has failed,

Refer to Chapter 8 for module

 

and requires replacement.

replacement procedure.

 

 

 

 

 

 

 

Intelligence Module is

The main intelligence module

Refer to Chapter 8 for module

 

has failed, and requires

 

installed and failed

replacement procedure.

 

replacement.

 

 

 

 

 

 

 

 

Redundant Intelligence

The redundant intelligence

Refer to Chapter 8 for module

 

Module is installed and

module has failed, and

 

replacement procedure.

 

failed

requires replacement.

 

 

 

 

 

 

Threshold

Load is above kVA alarm

The load has exceeded the

Option #1: Reduce the load.

user specified load alarm

Option #2: Use the PowerView to

Alarm

threshold

threshold.

raise the alarm threshold.

 

 

 

 

 

 

 

 

 

Option #1: If possible, install

 

 

SymmetraTM no longer detects

additional power modules.

 

 

Option #2: Decrease the load.

 

 

redundant power modules.

 

Redundancy has been

Option #3: Disable the

 

Either power module(s) have

 

lost.

redundancy alarm by setting

 

failed, or the load has

 

 

redundancy to zero. (Startup-

 

 

increased.

 

 

Setup-Alarms-Redundancy-

 

 

 

 

 

 

select zero.)

 

 

 

 

 

 

Actual power module

Option #1: If possible, install

 

 

additional power modules.

 

 

redundancy has fallen below

 

 

Option #2: Decrease the load.

 

Redundancy is below

the user specified redundancy

 

Option #3: Use the PowerView to

 

alarm threshold.

alarm threshold. Either

 

decrease the redundancy alarm

 

 

power module(s) have failed,

 

 

threshold. (Startup-Setup-Alarms-

 

 

or the load has increased.

 

 

Redundancy-select.)

 

 

 

 

 

 

 

 

 

 

Option #1: Allow the battery

 

 

The predicted runtime is

modules to recharge.

 

 

Option #2: If possible, increase

 

 

lower than the user specified

 

 

the number of battery modules.

 

Runtime is below alarm

minimum runtime alarm

 

Option #3: Decrease the load.

 

threshold.

threshold. Either the battery

 

Option #4: Use the PowerView to

 

 

capacity has decreased, or the

 

 

decrease the minimum runtime

 

 

load has increased.

 

 

alarm threshold. (Startup-Setup-

 

 

 

 

 

 

Alarms-Runtime-select.)

 

 

 

 

Bypass

 

The frequency and/or voltage

Option #1: Decrease the

 

 

is out of acceptable range for

 

 

sensitivity to input frequency.

 

 

bypass. This message occurs

 

Bypass is not in range

(Startup-Setup-OutputFreq-select.)

 

when SymmetraTM is on line,

 

(either freq or voltage)

Option #2: Corrrect input voltage

 

and indicates that the bypass

 

 

to provide acceptable voltage

 

 

mode may not be available if

 

 

and/or frequency.

 

 

required.

 

 

 

 

 

 

 

 

Bypass contactor stuck

SymmetraTM is stuck in the

Call your contract service

 

bypass position, and cannot go

provider, or APC Technical

 

in bypass position.

 

online.

Support. (See inside front cover.)

 

 

 

 

 

 

 

 

 

 