Chapter 1 - Physical Representation

Powerview User Interface

The Powerview incorporates a 4 x 20 alphanumeric LCD screen with four navigation keys, four LED status indicators, and an audible alarm beeper. The display communicates with the Power Array via a local RJ45 connector cable that is hardwired into the top power module bay. It can be mounted on the front of the frame, stand on top of the frame, or it can be installed at a remote location. (A 20’ RJ45 cable is provided, and plugs into a communication port at the rear of the frame.) The alphanumeric LCD screen displays system status, fault reporting and module diagnostics information. The naviga- tion keys are used to scroll through an elaborate menu. Chap- ter 6 provides detailed information about the Powerview.

LEDStatus Indicators

LCD Screen

Navigation Keys

Fig 1-3Powerview User Interface

Alarm thresholds and parameters are set with the Powerview. In the event of an alarm condition, the Powerview emits both audible and visual alarm indicators.

Louvered Grill Covers

Each level of the frame is equipped with a louvered grill cover. These covers are interchangable, and snap securely onto the frame. When removing, temporarily storing, and replacing grill covers, use care to prevent them from being marred or scratched.

Fig 1-3Front Grill Cover Removal and Replacement

Power Module

The power module is a self-contained, 4kVA UPS (without batteries) housed inside a metal enclosure. A blind mating connector at the rear of the module engages with a connector inside the frame, and powers the unit. Power modules are installed in the vertical column of bays at the left of the frame. These bays are labelled L1, L2, L3, etc.

Blind Mating

Connector

Positioning Handle

Cooling Fan Grill

Alignment Runner

Seating Tabs

Flip Latch Micro Switch

Fig 1-4Power Module

In the event of a power module failure, the Powerview initiates an audible alarm, and displays an error message. The power module is hot-swappable. Instructions for module replace- ment are provided in chapter 8.

Battery Module

The battery module is comprised of a series of ten 12V batter- ies housed inside a plastic enclosure. A blind mating connec- tor at the rear of the module engages with a connector inside the frame.

Blind Mating

Connector

Retaining Flange

Positioning Handle

Runners

Fig 1-5Battery Module

Battery modules are installed in the vertical column of bays at the right of the frame. These are labelled R2, R3, R4, etc. (The top right bay houses the intelligence modules.) The condition and charge of each battery module is reported on the PowerView. If a battery module fails, an alarm is initiated. Battery modules are hot-swappable, and user replaceable.