Chapter 9 - PowerView Display Messages
PowerView
Message
Meaning
Corrective Action
General
Status
# of batteries increased. | At least one battery module has | No corrective action necessary. | |
been added to the system. | |||
|
| ||
|
|
| |
# of batteries decreased. | At least one battery module has | No corrective action necessary. | |
been removed from the system. | |||
|
| ||
|
|
| |
# of Pwr Modules | At least one power module has | No corrective action necessary. | |
increased. | been added to the system. | ||
| |||
|
|
| |
# of Pwr Modules | At least one power module has | No corrective action necessary. | |
decreased. | been removed from the system. | ||
| |||
|
|
| |
Intelligence Module | A MIM has been installed into the | No corrective action necessary. | |
inserted. | SymmetraTM . | ||
| |||
|
|
| |
Intelligence Module | A MIM has been removed from the | No corrective action necessary. | |
removed | SymmetraTM . |
| |
|
|
| |
Redundant Intelligence | A RIM has been installed into the | No corrective action necessary. | |
Module inserted. | SymmetraTM . | ||
| |||
|
|
| |
Redundant Intelligemce | A RIM has been removed from the | No corrective action necessary. | |
Module removed. | SymmetraTM . | ||
| |||
|
|
| |
# of External Battery | At least one external battery cabinet | No corrective action necessary. | |
Cabinets increased. | has been connected to the frame. |
| |
|
|
| |
# of External Battery | At least one external battery | No corrective action necessary. | |
cabinets has been disconnected | |||
Cabinets decreased. | |||
from the SymmetraTM. |
| ||
|
| ||
|
|
| |
| A loss of power module redundancy |
| |
| occurred, and has been restored. |
| |
Redundancy Restored | Either additional modules have been | No corrective action necessary. | |
| installed, or the load has been |
| |
| reduced. |
| |
|
|
| |
| The load had exceeded the load |
| |
Load is No Longer above | alarm threshold. The situation has |
| |
been corrected either because the | No corrective action necessary. | ||
Alarm Threshold | load decreased, or the threshold |
| |
|
| ||
| was increased. |
| |
|
|
| |
| The system runtime had dropped |
| |
| below the configured minimum, and |
| |
| has been restored. Either additional |
| |
Min Runtime restored. | battery modules were installed, the | No corrective action necessary. | |
| existing battery modules recharged, |
| |
| the load was reduced, or the |
| |
| threshold was raised. |
| |
|
|
|