Chapter 6 - The PowerView Display

PowerView LED's

Four LED indicators report the operational status of the Power Array. Table 6-1 describes the function of each of the LED indicators.

LED

Color

Description

 

 

 

LOAD

Green

Indicates normal, on-

ON

 

line operating

 

 

condition. The Power

 

 

Array is on, is

 

 

receiving power from

 

 

the utility, and is

 

 

supplying clean,

 

 

conditioned power to

 

 

the load.

 

 

 

ON

Yellow

Indicates that a utility

BATT

 

power failure has

 

 

occured, and that

 

 

power to the attached

 

 

load is being supplied

 

 

by the battery

 

 

modules.

 

 

 

BYPASS

Yellow

Indicates that power

 

 

to the load is being

 

 

supplied directly from

 

 

the power utility. The

 

 

Power Array has been

 

 

effectively removed

 

 

from the circuit.

 

 

 

FAULT

Red

Indicates that the

 

 

Power Array has

 

 

detected an internal

 

 

fault condition. An

 

 

alarm message will

 

 

appear on the

 

 

PowerView display.

 

 

(See Chapter 9 for

 

 

appropriate corrective

 

 

action.)

 

 

 

Table 6-1Power Array Display LEDs

Navigation Keys

The four navigation keys located on the front of the Powerview interface are used to move through the screen menus, select menu items, and to either access information, or change sys- tem parameters. A small arrow at the left side of the display screen indicates which menu item or parameter is selected. The navigation keys are described in Table 6-2.

Table 6-2Navigation Keys Descriptions