Chapter 1 - Physical Representation

Rear View of a Power Array

The rear of a MiniFrame system is displayed below. The rear of a MasterFrame is similar. Each of the components are described in a section that follows:

System Enable Switch

The system enable switch regulates internal power to the Power Array. It does not power the load. When switched to the “on” position, the Power Array enters the load-disconnect operat- ing mode. When switched to “stand by” the Power Array is disconnected from incoming utility voltage. The load is not powered until the “power the load” command is entered into the PowerView interface.

Communication Interface Ports

The following three communication ports are provided: A remote PowerView cable port; an APC PowerChute Plus soft- ware interface port, and two battery extension frame com- munication ports. A 20’ RJ45 cable is provided with the Power Array for remote installation of the PowerView.

Smart SlotsTM Accessory Ports

APC manufactures a set of auxillary user interface accessories, called SmartSlotTM devices. Four SmartSlotTM installation ports are provided. SmartSlotTM interface options include:

Communication

Interface

Ports

Power Distribution

Unit (Optional)

System

Enable

Switch

Battery

Extension

Frame

Connector

REPO Wiring

Access Panels

νProtection and safe shutdown of multiple servers

νSNMP adaptor for accessing data via a network

νCallUPSTM - Initiates telephone notification of power event

νMeasureUPSTM - monitoring environmental conditions

νControl and monitor via modem

Note: Use only SmartSlotTM devices labelled “SymmetraTM compatible.”

REPO/Input/Output Wiring Access Panels

Wiring terminal blocks for input and output wiring, and for remote emergency power off (REPO) switch intallations are accessed through these panels. For use by a licensed electrian.

Power Distribution Unit Panel (Optional)

An optional power distribution unit provides output power receptacles and corresponding circuit breakers. The MiniFrame PDU provides one L6-30R receptacle (208V), two 5-15R recep- tacles (120V), and two L14-30R receptacles (120V/240V). The MasterFrame PDU provides three L6-30R receptacles, four 5- 15R receptacles, and three L14-30R receptacles. The PDU panel for both frame sizes are equipped with a panel circuit breaker.

Battery Extension Frame Connector

An optional Battery Extension Frame can be connected to the Power Array using this coupler. See the User’s Manual inluded with the Battery Extension Frame.

SmartSlotTM

Accessory

Ports

MiniFrame

Output

Wiring

Access

Panels

Input

Wiring

Access

Panels

Fig 1-8Rear View of a Mini Frame SymmetraTM Power Array System

1-4

Page 19
Image 19
American Power Conversion SYMSTRF-PD, SYMINIF-PD user manual Rear View of a Power Array