| Chapter 8 - Module Replacement |
Power Module Replacement |
|
The following section provides the procedure for replacing a |
|
power module. |
|
Removing the Power Module |
|
1. Remove the grill cover from in front of the module to be |
|
replaced. Note that the module bays are labelled to corre- |
|
spond with the PowerView display. |
|
2. If replacing a |
|
module to be replaced is the only power module present, the |
|
SymmetraTM must be placed in manual bypass mode, or the |
|
load equipment must be switched off. To place the SymmetraTM |
|
in manual bypass, switch the maintenance bypass switch to |
|
the “on” position. |
|
Note: When the SymmetraTM is in bypass mode, the load equip- |
|
ment is unprotected from power failure. | Drop Lock |
3. Use a flathead screwdriver to release the fliplatch from the | Seating Tabs |
power module. See figure |
|
Fig 8-7 Release the Flip Latch
4.Note the two drop lock seating tabs at the front of the power module. See Figure
5.Remove the power module from the frame. If the module has failed and needs to be disposed of, return it to the appro- priate service provider, or directly to APC.
Fig
Installing the Replacement Module
Refer to chapter 5 for the power module installation proce- dure.
Note: If SymmetraTM was placed in manual bypass in step 2 above, return to normal operation by switching the mainte- nance bypass switch back to the “off” position.
Replacement Module Verification
From the startup screen, press any key to open the top level menu screen. Follow the sequence in figure
Fig