Chapter 5 - System Setup

θ6. Press the down arrow key to scroll to the power mod- ule status screen. See figure 5-19.

Fig 5-19Power Status Screen

Verfiy that the number of power modules reported (3 in figure 5-19) is the same as the actual number of power modules that are installed. Verify that the number of “bad” modules re- ported is zero. The first line of the power status screen dis- plays the reported capacity of the SymmetraTM. The reported capacity is dependent upon the number of power modules installed, and the size of the frame. Use table 5-1 to confirm that the PowerView is reporting the correct information.

Number

Reported

Reported

of Power

Capacity in

Capacity in

Modules

MiniFrame

MasterFrame

 

 

 

1

4 kVA

4 kVA

 

 

 

2

8 kVA

8 kVA

 

 

 

3

8 kVA

12 kVA

 

 

 

4

n/a

16 kVA

 

 

 

5

n/a

16 kVA

 

 

 

Table 5-1SymmetraTM Power Module/Frame Capacities

θ7. Press the down arrow key to scroll to the miscellaneous status screen. See figure 5-20. The bottom line indicates the status of the MIM and RIM. The sample screen in figure 5-20 indicates that both are installed and functioning properly (OK). If a module is not installed, the status screen will display the word “NONE.” Confirm that the status of the MIM and RIM as indicated by this screen conforms to the actual installation of those modules. Use the ESC key to return to the startup screen.

Fig 5-20Miscellaneous Status Screen

θ8. Use the following steps to deliver output voltage to the

load equipment. See figure 5-21 for the screen sequence.

νPress the ESC navigation key on the PowerView display until the startup screen appears.

νPress the ESC key to display the top level menu.

νPress the down arrow navigation key, until the cursor is pointing to “Control.”

νPress the “enter” navigation key.

νPress the down arrow navigation key, until the cursor is pointing to “Turn Load ON.”

νPress the “enter” navigation key.

νConfirm that you want to turn the load on, by selecting “YES, Turn UPS ON”

νSeveral other over-ride messages may appear, depending on the system configuration. Select “start now” for any of these startup over-ride messages.

Fig 5-21Power The Load Sequence

After several seconds, the PowerView display should report that the“UPS LOAD IS ON.” Press the ESC key to return to the startup screen. Confirm that output voltage is present, and that the Load On LED is glowing.

Note: The Bypass LED may flash on briefly, and the On Battery LED may light for 20-30 seconds if the system is configured for “self test at power on.”

θ9. Perform a self test by following the screen sequence in figure 5-22.

Fig 5-22Initiate a Self Test Sequence

The On Battery LED should glow for approximately 30 sec- onds. A message will appear on the display indicating that a self test is in progress. When the“Self Test Complete”message appears, press any key to return to the startup screen.

5-8

Page 45
Image 45
American Power Conversion SYMSTRF-PD, SYMINIF-PD 19Power Status Screen, 1SymmetraTM Power Module/Frame Capacities