Chapter 4 - Electrical Requirements and Procedures
Output Wiring
Output voltage is delivered to the load equipment via hardwired connections and/or via receptacles on an optional power distribution unit (PDU). To facilitate maintenance and service of the Power Array, it is recomended that flexible metal conduit be used for all hardwiring connections.
See table
Output Wiring Configurations
The Power Array is typically wired to deliver either120V/240V, or 120V/208V/240V output voltages. The internal wiring to the output terminal block is depicted in figure
Note: Use only the connections shown in table
Voltage | Connections* |
|
|
120V | |
|
|
240V | |
|
|
208V | |
|
|
*Use only these connections. All other combinations will yield voltages other than normal utility voltages.
Table
Fig |
Neutral
Ground
Bond
.
Fig
Output Overcurrent Protection
SymmetraTM requires output voltage overcurrent protection in accordance with the ratings in table
Output | Frame | Maximum | Output | Minimum | Minimum | ||
Size | Overcurrent | Output | Ground | ||||
Voltage | Output Per | ||||||
(Max. kVA | Protection | Wire | Wire | ||||
| Conductor | ||||||
| Rating) | (External) | Gauge | Gauge | |||
|
| ||||||
|
|
|
|
|
| ||
120/240Vac | Mini (8kVA) | 40 Amp | 50 Amp | #8 Gauge | #8 Gauge | ||
|
|
|
|
|
| ||
Master (16kVA) | 80 Amp | 90 Amp | #3 Gauge | #3 Gauge | |||
|
|
|
|
|
|
| |
120/208/240Vac | Mini (8kVA) | 40 Amp | 50 Amp | #8 Gauge | #8 Gauge | ||
|
|
|
|
|
| ||
Master (16kVA) | 80 Amp | 90 Amp | #3 Gauge | #3 Gauge | |||
|
|
|
|
|
|
|
Table