American Power Conversion SYMINIF-PD PowerView Message Meaning Corrective Action General Fault

Models: SYMSTRF SYMINIF SYMSTRF-PD SYMINIF-PD

1 75
Download 75 pages 19.36 Kb
Page 70
Image 70

Chapter 9 - PowerView Display Messages

PowerView

Message

Meaning

Corrective Action

General

Fault

Fault, Internal Temp

The temperature of one or more

Replace the overheated modules.

Refer to chapter 8 for module

exceeded normal limits

battery modules is too hot.

replacement procedures.

 

 

 

 

 

 

 

Option #1: If this occurs in

 

 

conjunction with an overload

 

The input circuit breaker on the

condition, decrease the load and

 

reset the breaker.

Input circuit breaker

SymmetraTM has tripped.

Option #1: If no overload condition

tripped open

Input voltage is disconnected to

exists, reset breaker. If it trips again,

 

the SymmetraTM.

 

call your contract service provider,

 

 

 

 

or APC technical support at:

 

 

1-888-809-TECH

 

 

 

 

A cooling fan in the SymmetraTM

Call your contract service provider,

System level fan failed

or APC technical support at:

frame has failed.

 

1-888-809-TECH

 

 

 

 

 

 

The main intelligence module has

Replace the intelligence module.

The Redundant Intelligence

failed, and the RIM is functioning

Refer to chapter 8 for module

Module is in control

as the primary intelligence

replacement procedures.

 

module.

 

 

 

 

 

IIC inter-module

The communications between

Call your contract service provider,

the MIM and at least one other

or APC technical support at:

communications failed.

module has failed.

1-888-809-TECH

 

 

 

 

9-5

Page 70
Image 70
American Power Conversion SYMINIF-PD, SYMSTRF-PD user manual PowerView Message Meaning Corrective Action General Fault