American Power Conversion SYMINIF-PD, SYMSTRF-PD user manual 23Initiate a Self-Test Sequence

Models: SYMSTRF SYMINIF SYMSTRF-PD SYMINIF-PD

1 75
Download 75 pages 19.36 Kb
Page 46
Image 46

Chapter 5 - System Setup

θ10. Place the SymmetraTM into Bypass by following the screen sequence in figure 5-23.

Fig 5-23Initiate a Self-Test Sequence

The Bypass LED should light, and the PowerView display will indicate that the SymmetraTM is bypassed.

θ11. Return the SymmetraTM to the on-line mode of opera- tion by following the screen sequence in figure 5-24.

Fig 5-24Return to On-Line Sequence

The Bypass LED should go out, and the message “UPS IS OUT OF BYPASS” will appear on the PowerView display. Press any key to return to the startup screen.

θ12. Power down the load equipment by following the screen sequence in figure 5-25.

Fig 5-25Power Down the Load Sequence

From the Control menu, power down the load equipment by executing the UPS LOAD OFF command. After several sec- onds, the “UPS LOAD IS OFF” message is displayed. All LEDs on the PowerView should be off.

θ13. Power down the SymmetraTM by switching the system enable switch and the input circuit breaker to the “off” posi- tion. The installation procedure has now been completed.

5-9

Page 46
Image 46
American Power Conversion SYMINIF-PD, SYMSTRF-PD user manual 23Initiate a Self-Test Sequence, 24Return to On-Line Sequence