Chapter 4 - Electrical Requirements and Procedures

5.Make sure there are no loose strands and that the terminal connection screws are sufficiently tightened.

6.After the electrical wiring test/checklist is completed (end of this chapter), replace the REPO access panel.

Contact Closure REPO Switch Connection

Connect the contact closure REPO wiring to the terminal block as illustrated in figure 4-14 below.

Note: The factory installed jumper remains as shown.

Jumper Installed

Fig 4-14Dry Contact Switch

24 Vdc REPO Switch Connection

Connect the 24Vdc REPO wiring to the terminal block as illustrated in figure 4-15 below.

Note: The factory installed jumper must be removed.

24Vdc Power Source

Fig 4-1524Vdc EPO Switch

Electrical Wiring Test

The following test procedure will ensure the Power Array has been correctly hardwired. It is intended that the licenced electrician who installed Power Array will perform this test. A true RMS voltmeter is required for this procedure.

Before this test can be conducted, the main intelligence mod- ule (MIM) must be installed, and the PowerView display must be connected to the Power Array. Refer to chapter 5 for pro- cedures to install the MIM and the PowerView. The power and battery modules need not be installed to perform this test.

Note: This test is intended to verify the electrical connection to the Power Array, not to verify it’s operation or explain it’s us- age. In this procedure, you will be instructed to ignore PowerView messages, etc. Refer to chapters 6 & 7 for detailed information about the operation of the Power Array.

Electrical Wiring Test/Checklist

θ1. Make sure all three switches - system enable, mainte- nance bypass, and input circuit breaker are in the “off ” or “stand by” position. Make sure all load equipment is either turned off, or is unplugged from the Power Array.

θ2. Use a true RMS voltmeter to measure the input AC voltage at the terminal connections at the rear of the frame (bottom level).

Note: If input voltage is less than 156Vrms or greater than 276Vrms, check input wiring for errors. DO NOT PRO-

CEED UNTIL THE INPUT VOLTAGE IS WITHIN THIS RANGE.

Record the input voltage here: ____________________

θ3. Check for proper ground installation. If available, a ground ohmmeter should be used. Otherwise, check for continuity to building ground.

θ4. Switch the input circuit breaker to the “on” position.

θ5. Switch the system enable switch to the “on” position. Note: The Power Array may make a series of clicking sounds as it runs through an initial self test.

4-8

Page 34
Image 34
American Power Conversion SYMINIF-PD, SYMSTRF Electrical Wiring Test/Checklist, Contact Closure Repo Switch Connection