Troubleshooting

Troubleshooting

Troubleshooting

This section describes the solutions to possible hardware/firmware issues that could arise during the

common operation of a Modero touch panel.

Troubleshooting Information

Symptom

Solution

 

 

My NI Controller can’t obtain a

In requesting a DHCP Address, the DHCP Server can take up to a few

DHCP Address.

minutes to provide the address to the on-board Master.

 

• Verify there is an active Ethernet connection attached to the rear of

 

the NI-Series Controller before beginning these procedures.

 

• Select Diagnostics > Network Address, from the Main menu and

 

verify the System number.

 

• If the IP Address field is still empty, give the NI Controller a few

 

minutes to negotiate a DHCP Address and try again.

 

 

My NI Controller shows the same

In requesting a DHCP Address, the DHCP Server can take up to a few

IP Address after selecting DHCP

minutes to provide the address to the on-board Master.

Server and clicking the GET IP

When using a controller that has previously been used; there may be

Information button.

an instance where the IP Address was set as a fixed IP. In this case,

 

 

the address would need to be released so a new user could use a

 

DHCP server provided address.

 

• Access the HyperTerminal application and try to communicate to the

 

controller via the COM port.

 

• Type echo on and press ENTER to send the information to the unit.

 

• Type get ip to display the actual IP Address used by the unit.

 

• Release the static/fixed IP Addresses.

 

• Recycle power to the unit and retry obtaining a DHCP address

 

through NetLinx Studio 2.2.

 

 

My NI Controller still can’t obtain a

If the NI Controller is not connected directly to an open Ethernet wall

DHCP Address even after

connector, but is rather connected to an Ethernet Hub

completing the above

• Contact Technical Support for a resolution to issues with this type

troubleshooting tip.

of connection scenario.

 

 

 

I can’t detect the NI Controller and

The on-board Master is trying to establish communication.

my Status LED is blinking

• Give it a few moments and retry establishing communication using

irregularly.

NetLinx Studio 2.2.

 

 

• If the problem persists, cycle power to the unit and repeat the above

 

procedure. Another solution is to attempt communication via another

 

method (Program Port or IP).

 

• Refer to the Configuration and Firmware Update section on page 37

 

for more information.

 

 

NetLinx Studio only detects one of

Each Master is give a Device Address of 00000.

my connected Masters.

• Only one Master can be assigned to a particular System number. If

 

 

you want to work with multiple Masters, open different instances of

 

NetLinx Studio and assign each Master its own System value.

 

• Example: A site has an NXC-ME260/64 and an NI-4000. In order to

 

work with both units. The ME260/64 can be assigned System #1 and

 

the NI-4000 can then be assigned System #2 using two open

 

sessions of NetLinx Studio 2.2.

 

 

NetLinx Integrated Controllers

125

 

 

 

 