AMX NI-3000, NI-4000, NI-2000 instruction manual Upgrading the NI Controller Firmware via an IP

Models: NI-2000 NI-4000 NI-3000

1 134
Download 134 pages 57.78 Kb
Page 54
Image 54
Upgrading the NI Controller Firmware via an IP

Configuration and Firmware Update

11.Repeat steps 8 - 11 again (the last component will successfully be installed).

12.Click Close once the download process is complete.

The OUTPUT and INPUT LEDs alternately blink to indicate the Master is incorporating the new firmware. Allow the Master 20 - 30 seconds to reboot and incorporate the new firmware.

13.Right-click the System number and select Refresh System. This establishes a new connection to the System and populates the list with the current devices (and their firmware versions) on your system.

Upgrading the NI Controller Firmware via an IP

Use the information from the Network Addresses dialog to establish a new communication method to the Ethernet-connected Controller.

1.Obtain the IP Address of the on-board Master from your System Administrator if you do not have an IP Address for the on-board Master:

Follow steps outlined in either the Obtaining the Master’s IP Address (using

DHCP) section on page 42 to obtain the IP or Assigning a Static IP to the NetLinx

Master section on page 43 to assign the address.

2.Launch NetLinx Studio 2.2 (default location is Start > Programs > AMX Control Disc > NetLinx Studio > NetLinx Studio 2.2).

3.Select Settings > Master Communication Settings from the Main menu to open the Master Communication Settings dialog (FIG. 31).

FIG. 31 Assigning Communication Settings and TCP/IP Settings

4.Click the Communications Settings button to open the Communications Settings dialog.

5.Click on the NetLinx Master radio button (from the Platform Selection section) to indicate that you are working with a NetLinx Master (such as the NI-Series of Integrated Controllers).

6.Click on the TCP/IP radio button (from the Transport Connection Option section) to indicate you are connecting to the Master through an IP Address.

7.Click the Edit Settings button (on the Communications Settings dialog) to open the TCP/IP Settings dialog (FIG. 31).

 

48

NetLinx Integrated Controllers

 

 

 

Page 54
Image 54
AMX NI-3000, NI-4000 Upgrading the NI Controller Firmware via an IP, Assigning Communication Settings and TCP/IP Settings