Baldor BXII installation manual Digital inputs

Models: BXII

1 88
Download 88 pages 52.21 Kb
Page 25
Image 25
4.6.2 Digital inputs - X2

The inputs are conditioned using Schmitt trigger buffers. If an input is configured as edge triggered, the triggering pulse must have a duration of at least 1ms (one software scan) to guarantee acceptance by Mint. The use of shielded cable for inputs is recommended.

Active high: connect +24VDC to the input and 0V to pin 9 (CREF).

The digital inputs will be active when a voltage of +24VDC (greater than 12VDC) is applied to them and will sink a current of approximately 11mA each.

Active low: connect +24VDC to pin 9 (CREF) and 0V to the input.

The digital inputs will be active when grounded (<2V) and will source a maximum of 11mA each.

Note: Sustained input voltages above 28V will damage the inputs.

4.6.2 Digital inputs - X2

1

10 Manual background

Location

Connector X2

 

 

(Mating connector: Weidmüller BL 3.5/10, 3.5mm pitch)

 

 

 

Pin

Name

Mint keyword / description

 

 

 

1

DIN0

INX.0

 

 

 

2

DIN1

INX.1

 

 

 

3

DIN2

INX.2

 

 

 

4

DIN3

INX.3

 

 

 

5

DIN4

INX.4

 

 

 

6

DIN5

INX.5

 

 

 

7

DIN6

INX.6

 

 

 

8

DIN7

INX.7

 

 

 

9

Common

Common connection

 

 

 

10

Shield

Shield connection

 

 

 

Description

Eight general purpose optically isolated AC digital inputs.

Sampling interval: 1ms

The inputs are electrically identical to inputs DIN8 to DIN15 described in section 4.6.1.

MN1904

Input / Output 4-9

Page 25