The inputs are conditioned using Schmitt trigger buffers. If an input is configured as edge triggered, the triggering pulse must have a duration of at least 1ms (one software scan) to guarantee acceptance by Mint. The use of shielded cable for inputs is recommended.
Active high: connect +24VDC to the input and 0V to pin 9 (CREF).
The digital inputs will be active when a voltage of +24VDC (greater than 12VDC) is applied to them and will sink a current of approximately 11mA each.
Active low: connect +24VDC to pin 9 (CREF) and 0V to the input.
The digital inputs will be active when grounded (<2V) and will source a maximum of 11mA each.
Note: Sustained input voltages above 28V will damage the inputs.
4.6.2 Digital inputs - X2
1
10
Location | Connector X2 |
|
| (Mating connector: Weidmüller BL 3.5/10, 3.5mm pitch) | |
|
|
|
Pin | Name | Mint keyword / description |
|
|
|
1 | DIN0 | INX.0 |
|
|
|
2 | DIN1 | INX.1 |
|
|
|
3 | DIN2 | INX.2 |
|
|
|
4 | DIN3 | INX.3 |
|
|
|
5 | DIN4 | INX.4 |
|
|
|
6 | DIN5 | INX.5 |
|
|
|
7 | DIN6 | INX.6 |
|
|
|
8 | DIN7 | INX.7 |
|
|
|
9 | Common | Common connection |
|
|
|
10 | Shield | Shield connection |
|
|
|
Description
Eight general purpose optically isolated AC digital inputs.
Sampling interval: 1ms
The inputs are electrically identical to inputs DIN8 to DIN15 described in section 4.6.1.
MN1904 | Input / Output |