5.6.2 Underdamped response

5.6.2 Underdamped response

If the graph shows that the response is underdamped (it overshoots the demand, as shown in Figure 17) then the value for KDERIV should be increased to add extra damping to the move. If the overshoot is excessive or oscillation has occurred, it may be necessary to reduce the value of KPROP.

Measured 5-16 Operation position

Demand position

Figure 17 - Underdamped response

9.Click in the KDERIV and/or KPROP boxes and make the required changes. The ideal response is shown in section 5.6.4.

5-16 Operation

MN1904

Page 56