Wire Size and Protection Devices

Output Caution: Do not use power factor correction capacitors on the input power lines to the inverter or damage to the control may result.

All external control wiring to the inverter should be run in a separate conduit from all other wiring. The use of shielded twisted pair wire is recommended for all control wiring. The shield of the control wiring should be connected to control terminal CM of the inverter only. The other end of the shield should be taped to the wire jacket to prevent electrical shorts.

Conduit openings are provided at the bottom of the inverter housing to allow power and control wiring entrance to the control. Please refer to the inverter outline drawings located in Section 5 of this manual for sizes of the conduit openings.

The following tables show recommended wire size and protection devices along with recommended terminal tightening torques.

Wire Size and Protection Devices

 

Rated

Input/

Input

Input Fuses

Catalog No.

Output

 

 

HP

Wire

Breaker

Fast

Time

 

 

 

AWG Cu

 

Acting

Delay

 

 

 

 

ID101F50-E

0.5

14

240V/10A

240V/5A

240V/3A

ID10101-E

1

14

240V/15A

240V/10A

240V/6A

ID102F50-E

0.5

14

240V/10A

240V/5A

240V/3A

ID10201-E

1

14

240V/15A

240V/10A

240V/6A

ID10202-E

2

14

240V/20A

240V/20A

240V/12A

ID10203-E

3

14

240V/25

240V/25

240V/15

ID10205-E

5

12

240V/40

240V/35

240V/25

ID10401-E

1

14

480V/5A

480V/5A

480V/6A

ID10402-E

2

14

480V/10A

480V/10A

480V/12A

 

 

 

 

 

 

ID10403-E

3

14

480V/15

480V/15

480V/15

ID10405-E

5

14

480V/20

480V/20

480V/25

Input and output wire size is based on use of 60/75°C rated copper conductor wire.