Baldor ID101F50-E manual Level One Parameter Adjustments

Models: ID101F50-E

1 74
Download 74 pages 26.37 Kb
Page 42
Image 42
Level One Parameter Adjustments

Level One Parameter Adjustments

07-Last Fault - A view only parameter that displays the most recent fault condition along with the elapsed time from the last restart of the control and the fault occurrence. The elapsed time is indicated in 0.1 hour increments with 0.9 hour maximum displayed. The two left most digits displayed is the fault code and the right most digits is the elapsed time.

12-Output Frequency - A view only parameter that displays inverter output frequency in Hertz applied to the motor.

13-Output Voltage - A view only parameter that displays inverter output voltage as a percentage of line input voltage.

14-Output Current - A view only parameter that displays inverter output current in Amps RMS per phase. The accuracy of the displayed current is ±20% and should not be used for motor overload sizing.

15-Drive Load - A view only parameter that displays true part of motor current with motor power factor considered. The displayed value is shown as a percentage of parameter

03-Rated Current and has an accuracy of ±20%. Positive values indicate motoring and negative values will indicate a regenerative overhauling load.

16-Load Torque - A view only parameter that displays torque output of the motor. The displayed value is a percentage of rated motor torque. Positive values will indicate motoring and negative values indicate a regenerative overhauling load. This parameter is most useful in determining available motor torque when operating with output frequencies above the value set in parameter 53-Control Base Frequency.

17-Heatsink Temp - A view only parameter that displays the inverter heatsink temperature in degrees Centigrade.

Operation 3-7

Page 42
Image 42
Baldor ID101F50-E manual Level One Parameter Adjustments