Parameter 75-RELAY OUTPUT SELECT
Value Description
0Off
1Ready. Inactive at Fault, Low Voltage, Idle, and in Program Mode
2Fault
3Forward and Reverse Output, Output Frequency above 0.5 Hz
4Reverse Output, Output Frequency above 0.5 Hz
5Forward Output, Output Frequency above 0.5 Hz
6Output Frequency less than 0.5 Hz
7Output at Set Frequency
8Output Frequency greater than Parameter 36-Preset Speed #4 setting
9Running in Torque Limit
10Overtemperature Warning. Temperature is within 10 degrees C of maximum rating
Level Two Parameter Adjustments
02-Software Revision - A view only parameter that displays the software revision code of the installed software version.
03-Rated Current - A view only parameter that displays the factory set nominal output current of the inverter. The factory setting also serves as the 100% reference for all displayed output currents. The inverter continuous output current is 110% of the factory setting.
08-Second Fault - A view only parameter that displays the second most recent fault condition before the Last Fault along with the elapsed time from the last restart of the control and the fault occurrence. The elapsed time is indicated in 0.1 hour increments with 0.9 hour maximum displayed. The two left most digits displayed is the fault code and the right most digits is the elapsed time.
09-First Fault - A view only parameter that displays the most recent fault condition before the Last Fault along with the elapsed time from the last restart of the control and the fault