Recommended Terminal Tightening Torques

Recommended Terminal Tightening Torques

Catalog No.

Tightening Torques

 

Power Terminal TB1

Control Terminal Strip

All Series 10

10 In-Lb (1.13 Nm)

2 In-Lb (0.23 Nm)

Caution:

Do not use this control with any input

 

voltage other than stated on the control

 

nameplate. Use of control with wrong power

 

source can damage the control.

 

Main Circuit Wiring

 

External or remote motor overload protection

 

may be required by NEC or other regulator codes.

To External

 

Trip Circuit

 

M3

 

Motor

 

 

M2

 

T3

 

T2

 

 

M1

 

T1 GND

 

 

L3 *

 

 

L2

 

 

L1

 

50/60Hz

 

3 Phase Power

 

 

Heatsink

GND

Breaker or Fuse

Protection customer Tightening Torques Heatsink provided option

GND

* Note: L3 is not available on 115VAC input models.

See recommended tightening torques for terminal connectors.