Pre-Operation Checks
Check of Electrical Items
After completing all the installation steps and before applying line power to the system, carefully check the following items:
1.Verify AC line voltage at source matches control rating.
2.Inspect all power terminations for workmanship and tightness.
3.Verify control and motor are grounded to each other and the control is connected to earth ground.
4.Check incoming signal wiring for accuracy.
Be certain all brake coils, contactors, and relay coils have noise suppression. This should be an
WARNING: MAKE SURE THAT UNEXPECTED OPERATION OF THE MOTOR SHAFT DURING
Check of Motors/Couplings
Verify freedom of motion for all motor shafts and that all motor couplings are tight without backlash.
Verify the holding brakes, if any, are properly adjusted to fully release and set to the desired torque value.