Value Displayed
+ 600

Frequency), a setting of ª1º will display Output Current (parameter 14-Output Current), and a setting of ª2º will display Drive Load (parameter 15-Drive Load). A setting of 3-3000 will display RPM. To display an exact RPM number for a given motor rated speed, the value of Display Options is found by the following formula:

Value Displayed

20

(Output Frequency) + Display Option Value

For Example: To display 1800 RPM at 60 Hz use 600 as the Display Option value:

1800 20

60

87-Security Access Code - Sets if a security code will need to be entered before any parameter can be modified. If the Security State is active a security code will need to be entered before parameter changes can be made from the keypad. Setting the Security Access Code to ª0º will defeat the security system. In any case the user will have the ability to view the parameter values. Access is allowed for ten minutes after the last keystroke or until the control goes through a restart sequence. Press the PROG key twice within two seconds after programming to immediately reinstate the access code. The security access code can be set from any number between 001 and 999. When changing the Security Access Code parameter the old Access Code will not be displayed. The factory setting is 0.

Note: Please write down your chosen Security Access Code in a secure location. If you cannot gain entry into the security area to change a parameter, please contact BALDOR.

3-26 Operation