Baldor ID101F50-E manual Parameter 41-Parameter 47-DC BRAKE TIME, Braking Action / Function

Models: ID101F50-E

1 74
Download 74 pages 26.37 Kb
Page 53
Image 53
Parameter 41-Parameter 47-DC BRAKE TIME

 

Parameter 41-Parameter 47-DC BRAKE TIME

 

Value

Braking Action / Function

 

0

DC Braking Disabled

 

 

 

 

 

Timed DC Braking (Parameter Value Sets Braking Time)

When both FWD and REV Terminals are closed (active) and Parameter 21-OPERATING MODE = 2, 3, 4, 5, 6, or (Terminal Strip

0.05Start/Stop Control)

to When Speed Command is reduced to less than 0.1 Hz while in FWD or

4.95REV Run Mode

After a STOP Command and the output frequency is reduced to less than 0.1 Hz

Continuous DC Braking

5

When both FWD and REV Terminals are closed (active) and Parameter 21-OPERATING MODE = 2, 3, 4, 5, 6, or 7 (Terminal Strip Start/Stop Control)

When Speed Command is reduced to less than 0.1 Hz while in FWD or REV Run Mode

48-DC Brake Voltage - Sets the amount of DC Voltage applied to the motor windings to cause the motor to stop. Increasing the DC Brake Voltage setting will cause the motor to have more braking torque available for stopping. Caution should be exercised when adjusting this parameter since DC Injection Braking will cause additional motor heating if used in applications requiring frequent starts and stops. The adjustable range is from 0-15 % of parameter 52-Torque Boost setting.

3-18 Operation

Page 53
Image 53
Baldor ID101F50-E manual Parameter 41-Parameter 47-DC BRAKE TIME, Braking Action / Function, DC Braking Disabled