Electronic Pot Control Terminal Logic
Parameter 21-Operating Mode = 6 or 7
| COMMAND | | CONTROL TERMINALS | |
| DESCRIPTION | | | | |
| FWD | REV | PS1 | PS2 |
| STOP | OPEN | OPEN | X | X |
| Speed = 0 | CLOSED | CLOSED | X | X |
| FWD Decrease | CLOSED | OPEN | CLOSED | X |
| FWD Hold | CLOSED | OPEN | OPEN | OPEN |
| FWD Increase | CLOSED | OPEN | OPEN | CLOSED |
| REV Decrease | OPEN | CLOSED | CLOSED | X |
| REV Hold | OPEN | CLOSED | OPEN | OPEN |
| REV Increase | OPEN | CLOSED | OPEN | CLOSED |
X=Don't Care Condition.
31-Min Output Frequency - Sets a minimum output frequency provided to the motor. During operation the output frequency will not be allowed to go below the minimum output frequency unless the motor is starting from 0 Hz or is ramped to a stop. The available values are 0 to 400 Hz. The factory setting is 0 Hz.
32-Max Output Frequency - Sets a maximum output frequency provided to the motor. The available values are 20 to 400 Hz. The factory setting is 60 Hz.
42-Accel Time #1 - Sets the time in seconds for the output frequency of the inverter to linearly increase from 0 Hz to the frequency specified by parameter 32-Max Output Frequency. The adjustable range is from 0 Sec to 600 Sec.
43-Decel Time #1 - Sets the time in seconds for the output frequency of the inverter to linearly decrease from the frequency specified by parameter 32-Max Output Frequency to 0 Hz. The adjustable range is from 0 Sec to 600 Sec.