Baldor ID101F50-E manual Electronic Pot Control Terminal Logic, Parameter 21-Operating Mode = 6 or

Models: ID101F50-E

1 74
Download 74 pages 26.37 Kb
Page 44
Image 44
Electronic Pot Control Terminal Logic

Electronic Pot Control Terminal Logic

Parameter 21-Operating Mode = 6 or 7

 

COMMAND

 

CONTROL TERMINALS

 

 

DESCRIPTION

 

 

 

 

 

FWD

REV

PS1

PS2

 

STOP

OPEN

OPEN

X

X

 

Speed = 0

CLOSED

CLOSED

X

X

 

FWD Decrease

CLOSED

OPEN

CLOSED

X

 

FWD Hold

CLOSED

OPEN

OPEN

OPEN

 

FWD Increase

CLOSED

OPEN

OPEN

CLOSED

 

REV Decrease

OPEN

CLOSED

CLOSED

X

 

REV Hold

OPEN

CLOSED

OPEN

OPEN

 

REV Increase

OPEN

CLOSED

OPEN

CLOSED

X=Don't Care Condition.

31-Min Output Frequency - Sets a minimum output frequency provided to the motor. During operation the output frequency will not be allowed to go below the minimum output frequency unless the motor is starting from 0 Hz or is ramped to a stop. The available values are 0 to 400 Hz. The factory setting is 0 Hz.

32-Max Output Frequency - Sets a maximum output frequency provided to the motor. The available values are 20 to 400 Hz. The factory setting is 60 Hz.

42-Accel Time #1 - Sets the time in seconds for the output frequency of the inverter to linearly increase from 0 Hz to the frequency specified by parameter 32-Max Output Frequency. The adjustable range is from 0 Sec to 600 Sec.

43-Decel Time #1 - Sets the time in seconds for the output frequency of the inverter to linearly decrease from the frequency specified by parameter 32-Max Output Frequency to 0 Hz. The adjustable range is from 0 Sec to 600 Sec.

Operation 3-9

Page 44
Image 44
Baldor ID101F50-E manual Electronic Pot Control Terminal Logic, Parameter 21-Operating Mode = 6 or