If you want to change the day and time the unit exercises, simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF selection within the day of the week menu and press OK. The display will then scroll: EXERCISE CYCLE OFF.

Automatic Operation

The generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset level, the control board will signal the engine to crank and start.

When utility voltage is restored above a preset voltage level, the engine is signaled to shut down.

The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:

Utility Voltage Dropout Sensor

This sensor monitors utility source voltage.

If utility source voltage drops below about 70 percent of the nominal supply voltage, the sensor energizes a 3 second timer. The timer is used to ‘sense’ brownouts.

Once the timer has expired, the engine will crank and start.

Utility Voltage Pickup Sensor

This sensor monitors utility voltage. When utility voltage is restored above 80 percent of the nominal source voltage, a time delay starts timing and the engine will go to engine cool-down.

Engine Cool-down Timer

When utility power is sensed and the load transfers back to the utility source, the engine will go into a cool down period as described below:

If the generator has run for MORE than 5 minutes, once the utility transfer occurs, the engine will continue to run for about 1 minute before shutting down.

If the generator has run for LESS than 5 minutes, once the utility transfer occurs, the engine will continue to run until 5 minutes has elapsed before shutting down.

Setting Exercise Timer

The generator is equipped with an exercise timer. During the

NOTICE Items will flash until they are selected.

exercise period, the unit runs for approximately 20 minutes

SELE T DAY: Use the left or right arrow to toggle

and then shuts down. Electrical load transfer DOES NO

through the days of the week, Once the day is

occur during the exercise cycle (unless an utility power

selected, hit the “OK” button.

outage occurs).

 

 

SELECT HOUR: Use the left or right arrow to toggle

The generator will only enter the exercise cycle if the unit

through between 1 and 12. Choose the hour of day

is in the AUTO mode and this exact procedu e is followed.

you want the generator to exercise then hit the “OK”

To set the exercise timer:

NOT

button.

 

NOTICE The generator is set with a service code exercise

SELECT MINUTE: Use the left of right arrow to toggle

 

for

between :00 and :59. Choose the minute of the day

cycle setting of Tuesday at 2:00 P.M, Central Time. To change

the cycle setting, proceed to the following steps:

you want the generator to exercise then hit the “OK”

 

 

button.

1. Choose the day and time you want your REPRODUCTIONgenerator to

exercise.

 

SELECT AM/PM: Use the left of right arrow to toggle

2. Press and hold the left arrow and right arrow

between AM and PM. Once chosen, hit the “OK”

simultaneously for three seconds to enter the General

button.

Set-Up program mode. See General Set-Upflow chart

NOTICE During the weekly exercise cycle, the generator will

in Menu Section.

 

run for 20 minutes, but it will not supply power to the home.

3. Verify and/or set the time and date on the unit.

During the exercise cycle, the in-home monitor will continue

4. Go to the SET EXERCISE prompt and hit the “OK”

blinking the GENERATOR READY green LED.

 

button.